Solution Type Technical Instruction Sure Solution 2372928.1 : Eagle: Fake Fuse Alarm ***5210.0082 ** FUSE PANEL 41xx Alarm In Fuse Panel**
In this Document
Created from <SR 3-16767268281> Applies to:Oracle Communications EAGLE (Software) - Version EAGLE 46.0 and laterTekelec GoalThis document will help in clearing the fake fuse alarm in the STP. Customer is getting the following alarm. 9871.0082 ** FUSE PANEL 41xx Alarm in Fuse Panel But customer has only 1 frame configured, hence it is safe to say that the above alarm is fake and needs to be cleared
FRAME SHELF TYPE FAN SolutionInitial troubleshooting 1:- Try to switch-over the MASP 2:- Re-seat the MDAL
If the above procedure does not clear the alarm proceed for the following steps.
Next Level Troubleshooting =================
The below procedure is non-impacting but advised be followed in Maintenance Window. Following are the part-numbers for which this procedure was executed:
Control Shelf Backplane Part Number :- 850-0330-07 REV A Fuse and Alarm Panel Part Number :- 870-2320-03 REV C Theoretical Information:- The Rack Alarm Connectors (RALM) controls the alarm condition indicators on each control or extension frame fuse and alarm panel. J13, J15, J32, J46, J61, J68 on Control Shelf backplane 850-0330-06/07. In our case as the control shelf backplane part number is 850-0330-07 REV A, the details of RALM ports on the control shelf backplane is as below, · J13 - RALM0 (CF00) · J15 - RALM1 (EF00) · J32 - RALM2 (EF01) · J46 - RALM3 (EF02) · J61 - RALM4 (EF03) · J68 - RALM5 (EF04) The System has only one frame that is the Control Frame (CF00), but getting fake fuse alarm for Extension Frame 41XX (EF02) northstp 18-02-12 09:06:04 GMT EAGLE5 46.0.3-65.26.29 ***5210.0082 ** FUSE PANEL 41xx Alarm in Fuse Panel** The overall idea is to make the system understand that there is NO frame EF02 (4th frame) in the system. Please follow the below procedure carefully to clear the fake fuse alarm. * Unplug the cable from port J-13 Note:- Make sure the cable is securely connected.
More detailed info is mentioned in : https://docs.oracle.com/cd/E54396_01/docs.46/E54363-01_rev_a.pdf Page 221 ;> Alarm Cable Termination