Solution Type Technical Instruction Sure Solution 1937659.1 : Platform Power Cord Replacement Procedure
In this Document
Applies to:Sun Rack 1000-38 - Version Not Applicable to Not Applicable [Release NA]Sun Blade 6048 System - Version Not Applicable to Not Applicable [Release N/A] Sun SPARC Enterprise M4000 Server - Version Not Applicable to Not Applicable [Release N/A] Sun SPARC Enterprise M5000 Server - Version Not Applicable to Not Applicable [Release N/A] Sun Blade 8000 P System - Version All Versions to All Versions [Release All Releases] Information in this document applies to any platform. GoalReplace all power cords on the system, destroy and dispose of the old power cords SolutionDISPATCH INSTRUCTIONS WHAT SKILLS DOES THE ENGINEER/ADMINISTRATOR NEED: TIME ESTIMATE: 30 minutes FIELD ENGINEER/ADMINISTRATOR INSTRUCTIONS TOOLS REQUIRED: N/A WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? : For non-redundant power configurations the system will need to be down. For redundant power configurations the system may remain up WHAT ACTION DOES THE ENGINEER/ADMINISTRATOR NEED TO TAKE:
If you determine that the platform has redundant power, it is recommended to follow the redundant power supply procedure below instead of powering off the system. After replacing the affected power cords cut the female end of the cord off at least 4 inches from the plug and disposed of both pieces of the cord so they cannot be re-used. If the system does not have redundant power supplies:
If the platform does have redundant power supplies:
Replacing cords which are connecting the rack power strips to datacenter power
Please consult your system's service manual for detailed instructions. You can find your system's service manual here: https://www.oracle.com/technetwork/indexes/documentation/index.html?ssSourceSiteId=ocomen More information on this issue can be found at http://www.oracle.com/us/support/power-cord-replacement/index.html OBTAIN CUSTOMER ACCEPTANCE WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE: For non-redundant power configurations the system will need to be powered on. For redundant power configurations there is no action necessary PARTS NOTE: REFERENCE INFORMATION: Service Manual: https://www.oracle.com/technetwork/indexes/documentation/index.html?ssSourceSiteId=ocomen Attachments This solution has no attachment |
||||||||||||||
|