Solution Type Technical Instruction Sure Solution 1643520.1 : SPARC T5-2 : Fans are constantly running at 100% when "Flash Accelerator FX0" (F40 and F80)is installed.
In this Document
Created from <SR 3-8604567761> Applies to:SPARC T5-2 - Version All Versions to All Versions [Release All Releases]Information in this document applies to any platform. GoalSystem fans are continuously operating at 100% ,the system fans begin to generate loud noise when the system enters POST and probes the PCI boards. The System fans Hypervisor version: @(#)Hypervisor 1.12.5.b 2014/02/07 13:50
Which is then followed by: NOTICE: Entering OpenBoot. NOTICE: Fetching Guest MD from HV. NOTICE: Starting additional cpus. NOTICE: Initializing LDC services. NOTICE: Probing PCI devices. NOTICE: Finished PCI probing. <<<<<<<<<<<<<<<<< System FAN begins to operate at maximum level
SolutionThe "Flash Accelerator F40" must be installed in the following Sequence Slot Sequence: Slot 1,Slot 8, Slot 2 and Slot 7. The maximum number of "Flash Accelerator F40" card supported on a SPARC T5-2 is four, Once the "Flash Accelerator F40" are installed in the recommended sequence the system fans will operate at the normal level. "Flash Accelerator F80" must be installed in the following Sequence "1, 8 ,2, 7, 3, 6, 4, 5".