Sun Microsystems, Inc.  Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-71-1642972.1
Update Date:2017-07-11
Keywords:

Solution Type  Technical Instruction Sure

Solution  1642972.1 :   Component Error Detected. Component Name: /SYS/CABLE_CONN_STAT during the firmware upgrade to 2.1.3-4.  


Related Items
  • Sun Datacenter InfiniBand Switch 36
  •  
  • Exadata Database Machine X2-2 Hardware
  •  
Related Categories
  • PLA-Support>Sun Systems>SAND>Network>SN-SND: Sun Network Infiniband
  •  




In this Document
Goal
Solution
References


Created from <SR 3-8759882447>

Applies to:

Sun Datacenter InfiniBand Switch 36 - Version All Versions to All Versions [Release All Releases]
Exadata Database Machine X2-2 Hardware - Version All Versions to All Versions [Release All Releases]
Information in this document applies to any platform.

Goal

Customer found CABLE_CONN_STAT error in messages during the firmware upgrade to 2.1.3-4.


/var/log/messages:Mar 27 16:05:45 ddx02sw-ib2 PEF: Sensor 'CABLE_CONN_STAT' Type 0xC0 Data1 0x01 Entity 7 Instance 0
/var/log/messages:Mar 27 16:06:01 ddx02sw-ib2 PEF: Sensor 'CABLE_CONN_STAT' Type 0xC0 Data1 0x00 Entity 7 Instance 0

Solution

Collect an ILOM snapshot (Note 1062544.1) from the InfiniBand Switch and check if shows faulty.

If there are no faults then run the below commands and check if the Environment test PASSED and switch is healthy:

# env_test
# showunhealthy
# sminfo
# getmaster

If there is no indication of fault visible in env_test or in showunhealthy output , the sensor CABLE_CONN_STAT is not a problem and can be safely ignored.

These error messages may be generated during the upgrade of Firmware version to 2.1.3-4. These messages are reported due to restart of services envd in following (which happens during a firmware upgrade). These messages can safely be ignored.

Please note this document actually covers 2 possible scenarios for false alarms against /SYS/CABLE_CONN_STAT:

- During an IB switch firmware upgrade (i.e. This covers the multiple envd restarts during an IB switch firmware upgrade).

- During an envd restart.

Newer IB switch firmware versions, such as v2.1.4-1 or v2.1.5-1, no longer exhibit this behavior.

References

<BUG:16878215> - SMTP ALERTS FIRE DURING SWITCH UPGRADE

Attachments
This solution has no attachment
  Copyright © 2018 Oracle, Inc.  All rights reserved.