![]() | Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition | ||
|
|
![]() |
||||||||||||||
Solution Type Technical Instruction Sure Solution 1637047.1 : SL8500 - 3-Phase Power Rotation Question
In this Document
Applies to:Sun StorageTek SL8500 Modular Library System - Version All Versions and laterInformation in this document applies to any platform. GoalSL8500 3-Phase Power Rotation Question SolutionDuring pre-install planning the customer's electrician may ask if "the electrical phase rotation direction is an issue for the SL8500.” The SL8500 does not need a specific phase rotation when connected to its 3-Phase power source. The 3 "hot" lines from the site can be connected in any sequence to the 3 load terminals on a PDU in the SL8500. Attachments This solution has no attachment |
||||||||||||||
|