Solution Type Technical Instruction Sure Solution 1611994.1 : SL48 - How to Replace the Chassis Base Unit (FRU) on a SL48
In this Document
Oracle Confidential PARTNER - Available to partners (SUN). Applies to:Sun StorageTek SL48 Tape Library - Version All Versions to All Versions [Release All Releases]Information in this document applies to any platform. GoalTo replace the base unit of the SL48 if the robotics have failed SolutionDISPATCH INSTRUCTIONS Refer to the SL48 Service Manual for complete instructions, pictures and warnings prior to taking the following actions. Either login with the OCP (Operator Control Panel) or via the RMI (Remote Managment Interface) Note the settings down. The SL48 configuration details are on the controller and should be transfered across with the change of the base chassis. 2. Ensure the host activity as stopped. 3. Ensure there is no media in the drive(s), if so please remove this. 4. Power off the SL48. 5. Remove all cables, drive(s), magazines, power supply(s) and finally the controller. 6. Remove the SL48 from the rack. 7. Replace the base chassis. 8. Reinstall controller, power supply(s), magazines, drive(s) and all cables. 9. Power on the SL48. 10. Check the settings and configuration is correct. If not add again from your notes in step 1. 11. Test the SL48 and hand back to the customer OBTAIN CUSTOMER ACCEPTANCE Full components list More details of this procedure can be found in the Service guide located here: http://docs.oracle.com/cd/E25510_01/en/875-4225-12/875-4225-12.pdf Attachments This solution has no attachment |
||||||||||||||
|