Solution  1587657.1 :   Cable Clamp Installation Instructions for Sun Server X3-2L when used in Exadata  


Related Items
  • Exadata X3-2 Hardware
  •  
  • Exadata X3-8 Hardware
  •  
Related Categories
  • PLA-Support>Eng Systems>Exadata/ODA/SSC>Oracle Exadata>DB: Exadata_EST
  •  




Oracle Confidential PARTNER - Available to partners (SUN).
Reason: Internal only

Applies to:

Exadata X3-2 Hardware - Version All Versions and later
Exadata X3-8 Hardware - Version All Versions and later
Information in this document applies to any platform.

Goal

 Cable Clamp Installation Instructions for Sun Server X3-2L when used in Exadata.

Solution

Note:  This issue described here only applies to X3-2L when used in an Exadata configuration.  This issue does not apply to the standalone X3-2L general purpose server.

Issue:
Due to a problem on the Sun Server X3-2L system with reading of the /SYS/T_AMB temperature sensor, a new method for retaining and routing the Left Front Indicator Module (LFIM) cable has been developed.

The previous cable routing method uses Kapton tape to secure the cable. This is to be replaced by a cable routing method using Cable Clamp (P/N 10075042) contained within FRU 7071084.

Parts Needed:
2 x Cable Clamp (Manufacturer's P/N: 10075042)
1 x Alcohol Wipe (Oracle P/N: 250-1802-01)
[Oracle FRU 7071084 contains 28 Cable Clamps and 14 Alcohol Wipes;use 1 FRU per Exadata X3-2 Rack]

 Clips and Wipes

Procedure:

Note: Following all ESD precautions required when working on an open system.

1. Remove AC cords from X3-2L System.

2. Open X3-2L system and remove Air baffle.

3. Locate LFIM cable on the left side of the system when viewed from front.

4. Detach LFIM cable from socket labelled LFIM on the motherboard. This socket is beside the left most DIMM socket.

5. Remove all Kapton taped used to secure LFIM cable next to motherboard.

6. Open fan door and remove fan module nearest left side wall.

7. The LFIM cable should have some 90degree bends and be held in place by Kapton tape in the space next to the fan module. Loosen tape to free up a length of cable (3 inches). This extra length of cable should be carefully fed through the gap in the midwall being careful not to catch any of the cable insulation on the edge of the midwall.

8.The entire area where the new clips will be installed should be cleaned using the alcohol wipe. From the midwall block, clean the sheet metal back until you reach the motherboard battery.

9. The two clips should now be applied to the sheet metal, located as per the photo below. It is advised to install the second clip first, as it will be easier to measure.
     • The clips only need a few seconds to stick and cannot be repositioned once attached.
     • The second clip should be placed 125mm back from the midwall block. This places the clip beyond the end of the air baffle.
     • The first clip should be positioned so it's front edge is 4mm behind the midwall block. This small clearance allows the cable to exit the clip without catching on the midwall block. It also allows the clip to avoid contact with the air baffle.

10. The cable should then be routed using the fold locations in the photo below.

11. Any excess cable should be fed back through the midwall, and attached to the side wall with the tape that was loosened in the first step.

12. Plug the cable back into the LFIM socket on the motherboard.

13. Reinstall the Air Baffle and Top Cover and left most fan module

14. Attach AC cords and confirm operation of the Front Indicator Module LED's and T_AMB temperature sensor, both with the system in standby and host power on.


Complete installation of cable clips and routing of LFIM cable:

Route of Cable

This MOS document was created from the original PDF version by Olly Sharwood that is located in Issue #5 in Doc ID 1501450.1


Additional detail from Exadata Database Machine Hardware Current Product Issues (X3-2, X3-8) (Doc ID 1501450.1)

Issue #5:

Cell generates CL_TEMP alert for >32C when temperature of Storage Cell or data center is normal (5-32). The alert is a false reading caused by interference between the Front Indicator Module cable and Motherboard components due to mis-routing of the cable within the chassis. False readings anywhere from 30C (in a room of 22C ambient on adjacent units) up to 99C have been observed. The ambient sensor on X3-2L systems is located on the front indicator module near the power button and LED's and should be very close to room ambient under normal readings.  Note that ILOM has no threshold for this sensor so will not record a fault or warning message in it directly.

 