Solution Type Technical Instruction Sure Solution 1547807.1 : Mx-32 How to replace a Faulty Cabled Lower Bus Bar Assembly
In this Document
Oracle Confidential INTERNAL - Do not distribute to customer (OracleConfidential). Applies to:SPARC M6-32 - Version All Versions and laterSPARC M5-32 - Version All Versions and later Oracle SuperCluster M6-32 Hardware - Version All Versions and later Information in this document applies to any platform. GoalCAP PROBLEM OVERVIEW: Mx-32 How to replace a Faulty Cabled Lower Bus Bar Assembly To report errors or request improvements on this procedure, please go to My Oracle Support, and put a comment on Doc ID: 1547807.1 .
ESD Caution:
Contamination Caution:
Caution – Danger of electrocution: AC circuits in the server share current. Remove all sources of AC current from the server.
SolutionDISPATCH INSTRUCTIONS WHAT SKILLS DOES THE ENGINEER NEED: Mx-32 Product Training/Experience TASK COMPLEXITY: 4 TIME ESTIMATE: 300 minutes COLD replacement FIELD ENGINEER INSTRUCTIONS WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? Physical Domains must be shut down. Server must be powered off. WHAT ACTION DOES THE ENGINEER NEED TO TAKE:
Remove a Cabled Lower Bus Bar Assembly1. Halt and power down the server. -> stop /System Caution – Danger of electrocution: AC circuits in the server share current. Remove all sources of AC current from the server.
Remove AC Power from the server. 2. Remove the front filler panel M5-32 How to Service the Front Filler Panel Assembly 3. Remove the upper fan cage. M5-32 How to Replace a Faulty Upper Fan Cage Assembly 4. Unlock the I/O data cables from the cabled lower bus bars assembly. There are two metal locking levers on the I/O data cable. The metal locking levers push against plastic locking tabs on the cabled lower bus bars assembly. a. Push up slightly on the plastic locking tab, then pull down a metal lever. 5. Remove the T20 Torx screws that hold the upper ends of the red and black power cables to the bus bar assembly Note – Take care not to drop the screws. These are not captive screws.
6. Detach the lower section of the cabled lower bus bars assembly: Loosen two captive T20 Torx screws that hold the plastic housing of the cabled lower bus bars assembly to the midplane, then pull the assembly out of the midplane. Note – Do not place screws or other loose hardware on the “shelves” of the midplane. Small items can easily fall inside the cabinet.
Install a Cabled Lower Bus Bar Assembly Note – Do not remove the protective plastic covers from the connectors on the cable until you are ready to plug a cable connector into a socket.
1. Install the plastic block of the cabled lower bus bars assembly. a. Remove the plastic cover from the cable assembly. b. Insert the cable assembly into the socket on the midplane. Note – The cable connectors in the plastic block are keyed with flat tops. Align the tops in the plastic block to make it easier to insert the block in the midplane connector.
c. Tighten the captive T20 Torx screws to lock the cable assembly in place. 2. Use 12 T10 Torx screws to connect the six upper ends of the power cables to the bus bars. 3. Install the upper fan cage. M5-32 How to Replace a Faulty Upper Fan Cage Assembly 4. Install the front filler panel. M5-32 How to Service the Front Filler Panel Assembly 5. Restart the server. a) Reconnect AC Power to server b) Momentarily press the On/Standby button on the front LED panel. 6. Return the replaced component to Oracle. Place plastic cover(s) on the connectors of the component. Also return any extra covers that were included with the replacement component.
OBTAIN CUSTOMER ACCEPTANCE WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE: Restart software applications per applicable administration guides to resume system operation.
======================== Other info ===================== REFERENCE INFORMATION: Service Manual: https://www.oracle.com/technetwork/documentation/oracle-sparc-ent-servers-189996.html Attachments This solution has no attachment |
||||||||||||||||||||
|