Solution  1541169.1 :   Mx-32 How to Replace a Faulty Scalability Midplane to PSDB Cable - FAN  


Related Items
  • SPARC M5-32
  •  
  • SPARC M6-32
  •  
  • Oracle SuperCluster M6-32 Hardware
  •  
Related Categories
  • PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: SPARC-CAP VCAP
  •  


M5-32 How to Replace a Faulty Scalability Midplane to PSDB Cable

In this Document
Goal
Solution
 Removing the Power System Distribution Board to Scalability Midplane Cable
 Install the Power System Distribution Board to Scalability Midplane Cable


Oracle Confidential INTERNAL - Do not distribute to customer (OracleConfidential).
Reason: FRU CAP

Applies to:

SPARC M6-32 - Version All Versions and later
SPARC M5-32 - Version All Versions and later
Oracle SuperCluster M6-32 Hardware - Version All Versions and later
Information in this document applies to any platform.
This component is cold service only. The factory description for this cable is “CABLE ASSY, SCMP-PSDB, FAN”. The process to replace this cable is complex and may require assistance from TSC.

Goal

CAP PROBLEM OVERVIEW: Mx-32 How to Replace a Faulty Scalability Midplane to PSDB Cable


To report errors or request improvements on this procedure, please go to My Oracle Support, and put a comment on Doc ID: 1541169.1



 

ESD Caution:
  • Circuit boards and drives contain electronic components that are  extremely sensitive to static electricity. Ordinary amounts of static electricity from clothing or the work environment can destroy the components located on these boards. Do not touch the components along their connector edges.
  • Use a Antistatic Wrist strap. Attach one end of the strap to your wrist and the other end to the chassis, depending on what type of strap you use, with the adhesive end or the metal plug.
  • Use an Antistatic Mat. Place ESD-sensitive components such as motherboards, memory, and other PCBs on an antistatic mat.

 

Contamination Caution:
  • Dust particles of packaging material are number one cause of datacenter contamination. Make sure to remove all packaging material, up to the ESD safe packaging material, while still being outside the datacenter.

Solution

DISPATCH INSTRUCTIONS

WHAT SKILLS DOES THE ENGINEER NEED: Mx-32 Product Training/Experience

TASK COMPLEXITY: 4

TIME ESTIMATE: 180 minutes COLD replacement

FIELD ENGINEER INSTRUCTIONS

WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :

Physical Domains must be shut down. Server must be powered off. 

WHAT ACTION DOES THE ENGINEER NEED TO TAKE:

 

Removing the Power System Distribution Board to Scalability Midplane Cable

Caution – For access to the cable, the server must be powered down so that the components shown below can be removed. It is highly recommended that the procedure outlined in the "M5-32 Service Manual starting on page 233 be reviewed.
Note - Prior to taking the server down for this procedure, it is recommended that you unpack and inspect the replacement cable. If there is any question about damage to the cable, do not use it.

1. Halt the server and turn off all AC power:

  • Turn the key switch on the Front Panel of the server to the Service position.
  • Gracefully shutdown the server by running the ILOM command "stop /System" (requires Oracle ILOM Reset and Host Control (r) user role).
  • Turn off all external breakers for the server.
  • For maximum safety, disconnect all six power cords from their respective AC outlets.

2. Verify that it is safe to disconnect the  power cords:

  • All six external breakers for the server must be in the Off position.
  • All six power cords for this server must be unplugged from their respective AC outlets.
  • No LEDs on the server should be lighted.
  • You should not hear any fans running in the server.

3. Remove the front filler panel. See M5-32 How to Service the Front Filler Panel Assembly [ID 1539427.1]  for details.
4. Remove all 16 Fan modules from the Upper Fan Cage and Remove all 16 Fan modules from the Lower Fan Cage. See M5-32 How to replace a Faulty Fan Module [ID 1530231.1] for details.
5. Remove all Service Processors and Service Processor Proxies from the Scalability Cage. See M5-32 - How to Replace a Faulty Service Processor (SP) [ID 1529334.1] for details.
6. Remove both Clock Boards from the Scalability Cage. See M5-32 - How to Replace a Faulty Clock Board [ID 1528995.1] for details.
7. Remove all 12 Scalability Switch Boards from the Scalability Cage. See M5-32 - How to Replace a Faulty Scalability Switch Board (SSB) [ID 1529636.1] for details.
8. Remove all 4 Fan modules from the Scalability Cage. See M5-32 How to replace a Faulty Fan Module [ID 1530231.1] for details.
9. Remove the upper fan cage. See M5-32 - How to Replace a Faulty Upper Fan Cage Assembly [ID 1531620.1] for details.
10. Remove the Scalability Card Cage. See M5-32 How to Replace a Faulty Scalability Card Cage [ID 1546735.1] for details.
11. Remove the lower fan cage. See M5-32 - How to Replace a Faulty Lower Fan Cage Assembly [ID 1531637.1] for details.
12. Remove the scalability assembly. See M5-32 How to replace a Faulty Scalability Assembly [ID 1538201.1] for details.
13. Remove T20 Torx screws from the three side brackets that hold the collection of cables to the side of the server.

Caution – Take care not to drop the screws. These are not captive screws.


14. Undo two T20 Torx screws to remove the upper end of the cable and metal single-connector bracket from the right side of the server.
15. Undo two T20 Torx screws to remove the lower end of the cable and metal three-connector bracket from the right side of the server.
16. Remove the cable from the server.

Install the Power System Distribution Board to Scalability Midplane Cable


1. Use a grounding strap to protect the equipment from ESD damage.
2. Unplug the faulty cable from the upper bracket.
3. Plug the replacement cable into the upper bracket. Both ends of the replacement cable are identical, so it doesn’t matter which end you use.
4. Use a cable tie to securely hold the upper end of the faulty cable to the lower end of the replacement cable.
5. Pull the faulty cable down to pull the replacement cable into the interior of the server.
6. Use two T20 Torx screws to attach the upper bracket and replacement cable to the right side of the server.
7. Separate the replacement cable from the failed cable. Open or cut the cable tie and remove the failed cable.
8. Plug the lower end of the replacement cable into the lower three-connector socket.
9. Use two T20 Torx screws to attach the lower bracket to the right side of the server.
10. Plug the upper end of the replacement cable to the front LED panel.
11. Install the metal side brackets that were removed in Step 9 of “Remove the Power System Distribution Board to Scalability Midplane Cable” on page 233.
12. Install the scalability assembly. See M5-32 How to replace a Faulty Scalability Assembly [ID 1538201.1] for details.
13. Install the lower fan cage. See M5-32 - How to Replace a Faulty Lower Fan Cage Assembly [ID 1531637.1] for details.
14. Install the scalability card cage. See M5-32 How to Replace a Faulty Scalability Card Cage [ID 1546735.1] for details.
15. Install the upper fan cage. See M5-32 - How to Replace a Faulty Upper Fan Cage Assembly [ID 1531620.1] for details.
16. Install 4 Fan modules in the Scalability Cage. See M5-32 How to replace a Faulty Fan Module [ID 1530231.1] for details.
17. Install all 12 Scalability Switch Boards in the Scalability Cage. See M5-32 - How to Replace a Faulty Scalability Switch Board (SSB) [ID 1529636.1] for details.
18. Install both Clock Boards. See M5-32 - How to Replace a Faulty Clock Board [ID 1528995.1] for details.
19. Install all Service Processors and Service Processor Proxies. See M5-32 - How to Replace a Faulty Service Processor (SP) [ID 1529334.1] for details.
20. Install all 16 Fan modules in the Upper Fan Cage and Remove all 16 Fan modules in the Lower Fan Cage. See M5-32 How to replace a Faulty Fan Module [ID 1530231.1] for details.
21. Install the front filler panel. See M5-32 How to Service the Front Filler Panel Assembly [ID 1539427.1]  for details.
22. Verify all six external breakers are still in the Off position.
23. Warn bystanders that you are preparing to restart the server.
24. Turn on all AC power and start the server:

  • Connect all six AC cords to their respective AC outlets.
  • Turn on all external breakers for the server.
  • Turn the key switch on the Front Panel of the server to the On position.
  • Start the server by running the ILOM command "start /System" (requires Oracle ILOM Reset and Host Control (r) user role).

25. Prepare the failed cable outside the datacenter for return to Oracle.