Solution Type Technical Instruction Sure Solution 1536841.1 : Mx-32 How to Replace a Faulty Fan Power Cable
In this Document
Oracle Confidential INTERNAL - Do not distribute to customer (OracleConfidential). Applies to:SPARC M6-32 - Version All Versions and laterSPARC M5-32 - Version All Versions and later Oracle SuperCluster M6-32 Hardware - Version All Versions and later Information in this document applies to any platform. GoalCAP PROBLEM OVERVIEW: Mx-32 How to Replace a Faulty Fan Power Cable To report errors or request improvements on this procedure, please go to My Oracle Support, and put a comment on Doc 1536841.1
ESD Caution:
Contamination Caution:
SolutionDISPATCH INSTRUCTIONS WHAT SKILLS DOES THE ENGINEER NEED: MX-32 Product Training/Experience TASK COMPLEXITY: 4 TIME ESTIMATE: 120 minutes FIELD ENGINEER INSTRUCTIONS WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? Physical Domains must be shut down. Server must be powered off. This component is COLD service only. WHAT ACTION DOES THE ENGINEER NEED TO TAKE: 1. Halt and power down the server. 2. Use a T20 Torx screwdriver to remove four mounting screws from the front filler panel. 3. Pull the front filler panel out of the slot. 4. Remove the upper fan cage. (see M5-32 How to Replace a Faulty Upper Fan Cage Assembly ) 5. Remove the scalability cage (see M5-32 How to Replace a Faulty Scalability Cage ) 6. Remove the lower fan cage. (see M5-32 How to Replace a Faulty Lower Fan Cage Assembly ) 7. Remove the scalability assembly (see M5-32 How to Replace a Faulty Scalability Assembly ) 8. Locate the faulty cable. The same cable can used in two separate places. Identify which cable that you intend to replace. 9. Undo the T20 shoulder screws on connectors P3 and P4. Caution – Take care not to drop the screws. These are not captive screws . 10. Undo the T20 shoulder screws on connectors P3 and P4. 11. Replace the fan power cable 12. Connect the T20 shoulder screws to attach connectors P3 and P4 to brackets on the side of server cabinet 13. Use T20 spring screws to attach connectors P1 and P2 to the midplane. 14. Install the scalability assembly (see M5-32 How to Replace a Faulty Scalability Assembly ) 15. Install the lower fan cage. (see M5-32 How to Replace a Faulty Lower Fan Cage Assembly ) 16. Install the scalability cage (see M5-32 How to Replace a Faulty Scalability Cage ) 17. Install the upper fan cage. (see M5-32 How to Replace a Faulty Upper Fan Cage Assembly ) 18. Re-install the front filler panel. Use a T20 Torx screwdriver to install four mounting screws in the panel. 19. Turn on AC power to the server. 20. Restart the server. 21. Return the faulted component to Oracle. OBTAIN CUSTOMER ACCEPTANCE WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE: Restart software applications per applicable administration guides to resume system operation.
======================== Other info ===================== REFERENCE INFORMATION: Service Manual: https://www.oracle.com/technetwork/documentation/oracle-sparc-ent-servers-189996.html Attachments This solution has no attachment |
||||||||||||||||
|