Solution  1530023.1 :   Fujitsu M10-4/M10-4S - How to Replace a PSU Backplane  


Related Items
  • Fujitsu M10-4S
  •  
  • Fujitsu M10-4
  •  
Related Categories
  • PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: SPARC-CAP VCAP
  •  




In this Document
Goal
Solution


Oracle Confidential PARTNER - Available to partners (SUN).
Reason: FRU CAP

Applies to:

Fujitsu M10-4S - Version All Versions to All Versions [Release All Releases]
Fujitsu M10-4 - Version All Versions to All Versions [Release All Releases]
Information in this document applies to any platform.

Goal

 M10-4S server - How to replace a PSU backplane

********************************************************************************
To report errors or request improvements on this procedure,
please go to http://support.us.oracle.com and put a comment on Doc ID: 1530023.1
********************************************************************************

Solution

 

DISPATCH INSTRUCTIONS


WHAT SKILLS DOES THE FIELD ENGINEER/ADMINISTRATOR NEED?: Engineer should be M10-4S trained

TIME ESTIMATE: 90 minutes

TASK COMPLEXITY:3

FIELD ENGINEER/ADMINISTRATOR INSTRUCTIONS:

PROBLEM OVERVIEW:


WHAT STATE SHOULD THE SYSTEM BE IN PRIOR TO PERFORMING THE RESOLUTION ACTIVITY?:

 

This activity can only be performed as a cold replacement.

 

WHAT ACTION DOES THE FIELD ENGINEER/ADMINISTRATOR NEED TO TAKE?:

 

  1. Login to the active XSCF

  2. In building block config, ID the target server and release it from the system via the replacefru command. 
    In a standalone config, poweroff the system.

  3. Remove all power cords from the server

Getting to the PSU backplane

For additional details about any of the steps below, please see the M10-4S service manual.

  1. Lower the cable support

  2. Remove all pci cables. In building block config, also remove cross bar cables and XSCF connection cables

  3. Remove all PCI cassettes and for empty slots remove the fillers

  4. Remove the crossbar units

  5. Loosen the 3 screws on the crossbar units to remove the crossbar frame

  6. Loosen the screw on the CPU memory unit and move the left and right levers to the horizontal position

  7. Slide the CPU memory unit out about 4 inches

  8. Remove the front cover

  9. Remove all the power supplies

  10. Remove all the fans

  11. Remove all the internal disks

  12. Loosen the 2 screws in the fan slot and remove the fan shelf

 

Removing the PSU backplane

  1. Loosen the 2 screws on the PSU backplane

  2. Pull out the PSU backplane by its handle

  3. Remove the operation panel from the PSU backplane

 

Installation of the PSU backplane

  1. Install the operation panel on the new PSU backplane

  2. Insert the PSU backplane by its handle

  3. Tighten the 2 screws on the PSU backplane

 

Re-install the remaining components

  1. Install the fan shelf and tighten the 2 screws

  2. Install the internal disks

  3. Install the fans

  4. Install the power supplies

  5. Install the front cover

  6. Slide the CPU memory unit back into the chassis, move the levers to the secure position and tighten the screw

  7. Install the crossbar frame and tighten the 3 screw

  8. Install the crossbar units

  9. Install all the PCI cards and fillers

  10. Connect all the PCI cables. In building block config, also reconnect the crossbar cables and the XSCF connection cables

  11. Raise the cable support

 

Finishing

  1. Reconnect all the power cables to the server

  2. Login to the XSCF

  3. In building block config, use replacefru to incorporate the server into the system

  4. Poweron the partitions to verify everything is working

 

OBTAIN CUSTOMER ACCEPTANCE

 

WHAT ACTION DOES THE FIELD ENGINEER/ADMINISTRATOR NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE?:

 

No additional work is required

PARTS NOTE: None

REFERENCE INFORMATION:

Service Manual - http://docs.oracle.com/cd/E38160_01

For a complete procedure, please see the M10-4S service manual

 