Solution Type Technical Instruction Sure Solution 1529699.1 : How to replace a Fan in a Crossbar box
In this Document
Oracle Confidential INTERNAL - Do not distribute to customer (OracleConfidential). Applies to:Fujitsu M10-4S - Version All Versions to All Versions [Release All Releases]Information in this document applies to any platform. Goal CAP PROBLEM OVERVIEW: How to replace a Fan in a Crossbar box SolutionDISPATCH INSTRUCTIONS WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?) Field training in M10-4S servers TASK COMPLEXITY: 2 Time Estimate: 30 minutes FIELD ENGINEER INSTRUCTIONS WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY?: All types of maintenance are available for the Fan unit, but the easiest is Active/hot maintenance. For the other maintenance types see the M10 Service Manual
1. Execute the XSCF> replacefru command to isolate the target Fan unit from the Crossbar box 2. Remove the front cover 3. Pull out the fan unit while raising the lever of the fan unit. Fan units are numbered starting from the left 0 to 3 4. Replace the Fan unit 5. Replace the front cover 6. Execute the XSCF> replacefru command to restore the Fan to Service
OBTAIN CUSTOMER ACCEPTANCE WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE: Verify the status of all domains. PARTS NOTE: REFERENCE INFORMATION: Service Manual - http://docs.oracle.com/cd/E38160_01