Solution  1503118.1 :   Sun SPARC(R) Enterprise M3000/M4000/M5000 (OPL) Servers: Power Specifications  


Related Items
  • Sun SPARC Enterprise M4000 Server
  •  
  • Sun SPARC Enterprise M3000 Server
  •  
  • Sun SPARC Enterprise M5000 Server
  •  
Related Categories
  • PLA-Support>Sun Systems>SPARC>Enterprise>SN-SPARC: Mx000
  •  




In this Document
Goal
Solution


Created from <SR 3-6392600064>

Applies to:

Sun SPARC Enterprise M3000 Server - Version All Versions and later
Sun SPARC Enterprise M5000 Server - Version All Versions and later
Sun SPARC Enterprise M4000 Server - Version All Versions and later
Information in this document applies to any platform.

Goal

What is the maximum power draw of the M3000 and M4000/M5000 servers?
 

Solution

The power requirements for the M4000/M5000 server are found into the "SPARC Enterprise M4000/M5000 Servers Site Planning Guide" that is available here, at the following section:

  • 2.4 Electrical and Cooling Specifications
    • TABLE 2-8 Midrange Servers Electrical Specifications
 

M4000 Server

M5000 Server

Number of power cords

2 (1 power cord per power supply unit)

4 (1 power cord per power supply unit)

Redundancy

1 + 1 redundant

Second power supply is redundant at 200 VAC

2 + 2 redundant

Second and fourth power supplies are redundant at 200 VAC

 

Input voltage

 

100-127 VAC

200-240 VAC

100-127 VAC

200-240 VAC

 

Maximum current

24.0A at 100-127 VAC (12A/cord)

12.0A at 200-240 VAC (12A/cord)

48A at 100-127 VAC (12A/cord)

24A at 200-240 VAC (12A/cord)

 

Frequency

50-60 Hz

50-60 Hz

 

Power draw (maximum)

 

1,692W (2 power cords)

3,270W (4 power cords)

Rush current per PSU[5]

 

50A

50A

Leakage current per PSU[6]

1.5mA

1.5mA

Volt ampere

1,763 VA

3,406 VA

 

Heat

5,774 BTUs/hr (6,091 kJ/hr)

11,160 BTUs/hr (11,772 kJ/hr)

 

Power factor

0.98

0.98

 

Note - Note - The values of power consumption represent power requirements of the system under highest achieved stress and utilization. Contact your authorized service engineer for the applicable power requirements.

     
 

Location

Power Cord Type

Connector Type

M4000 Server

Americas, Taiwan, Korea, Japan

NEMA L5-15 125V 15A

NEMA L6-20 250V 20A

 

IEC 60320 C19

 

Rest of the world

IEC 60309 16A 250V

 

 

3PIN with

IEC 60320 C20

M5000 Server

 

Americas, Taiwan, Korea, Japan

NEMA L5-15 125V 15A

NEMA L6-20 250V 20A

 

IEC 60320 C19

 

Rest of the world

 

IEC 60309 16A 250V

 

3PIN with

IEC 60320 C20

Note - For servers that have the plug with lock function, confirm that a 20A overcurrent protection device is available outside the server. If one is not available, prepare an external 20A overcurrent protection that can be achieved by means of no-fuse breakers (NFBs) or fuses. The plug with lock function refers to plugs other than grounding-type ones with two parallel blades, such as the NEMA L6-30, L6-20, L6-15, and L5-15.

 

 

The power requirements for the M3000 server is found into the "SPARC Enterprise M3000 Server Site Planning Guide" that is available here, at the following section:

  • 3.3 Power Requirements
    • TABLE 3-4 Electrical Specifications

power reference

 

 

 

To discuss this information further with Oracle experts and industry peers, we encourage you to review, join or start a discussion in an appropriate
My Oracle Support Community - Oracle Sun Technologies Community.

 


Attachments
This solution has no attachment
  Copyright © 2018 Oracle, Inc.  All rights reserved.
 Feedback