Solution Type Technical Instruction Sure Solution 1488424.1 : How to Remove and Replace Sun Fire V250 Rear Cooling Fans:ATR:1488424.1:1
In this Document
Oracle Confidential (INTERNAL). Do not distribute to customers. Applies to:Sun Fire V250 Server - Version All Versions to All Versions [Release All Releases]Information in this document applies to any platform. GoalSun Fire V250 - How to Remove and Replace Sun Fire V250 Rear Cooling Fans Fix DISPATCH INSTRUCTIONS Sun Fire V250 product training is desirable but not required TIME ESTIMATE: 45 mins TASK COMPLEXITY: 1
A data backup is not a pre-requisite but is a wise precaution. WHAT ACTION DOES THE FIELD ENGINEER/ADMINISTRATOR NEED TO TAKE?: Rear Cooling Fans The Sun Fire V250 server has one cooling fan module in the back, which contains two fans. Remove and replace the module as a single unit. To Remove the Fan Module 1. Turn server power off. 2. Remove the service panel. 3. Disconnect the fan module power cables from the system board. 4. Unclip the fan retaining tab. 5. Rotate the fan module out and remove it from the chassis. To Replace the Fan Module 1. Insert the replacement fan module. 2. Connect the fan power cables to the system board. 3. Replace the service panel.
Restart software applications per applicable administration guides to resume system operation.
https://support.oracle.com/handbook_private/Systems/SunFireV250/components.html
Please refer to the Sun Fire V250 Parts Replacement Manual: http://docs.oracle.com/cd/E19088-01/v250.srvr/817-0901-10/817-0901-10.pdf Attachments This solution has no attachment |
||||||||||||||
|