How to remove and replace a SPARC Enterprise T5440 Fan Tray:ATR:1389949.1:0
Related Items |
- Sun SPARC Enterprise T5440 Server
|
Related Categories |
- PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: SPARC-CAP VCAP
|
In this Document
Applies to:
Sun SPARC Enterprise T5440 Server - Version All Versions and later
Information in this document applies to any platform.
Goal
*************************************************************************************
To report errors or request improvements on this procedure, please Add a comment on Doc ID: 1389949.1
*************************************************************************************
How to remove and replace a T5440 Fan Tray
Solution
DISPATCH INSTRUCTIONS
WHAT SKILLS ARE REQUIRED?: No special skills required, Customer Replaceable Unit (CRU) procedure
TIME ESTIMATE: 30 minutes
Task Complexity: 0
REMOVAL/REPLACEMENT INSTRUCTIONS:
PROBLEM OVERVIEW: Fan tray failure
WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? : N/A (Fan Trays are hot-swappable)
WHAT ACTIONS ARE REQUIRED?:
A) Remove a Fan Tray
1. Extend the server to the maintenance position.
2. Lift the latch and open the top cover door.
3. The faulty fan tray is identified with a corresponding fault LED.
4. Press the fan tray latches toward the center of the fan tray and pull the fan tray up and out of the system until you remove the fan tray from the chassis.
B) Install a Fan Tray
1. With the top cover door open, install the replacement fan tray into the server.
2. Apply firm pressure to fully seat the fan tray.
3. Verify that the Fan Fault LED on the replaced fan tray is off.
4. Close the top cover door.
5. Verify that the system Fan Fault LED, Service Required LEDs, and the individual fan tray Fault LED are off.
6. Run the ILOM 'show faulty' command to verify that the fan fault has been cleared.
NOTE: If you are replacing a faulty fan tray due to an overtemperature condition, monitor the system to ensure proper cooling.
OBTAIN CUSTOMER ACCEPTANCE
WHAT ACTIONS ARE REQUIRED TO RETURN THE SYSTEM TO AN OPERATIONAL STATE?: N/A