How to Replace Sun Fire X2270 M2 Memory DIMM
Related Categories |
- PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: x64-CAP VCAP
|
In this Document
Applies to:
Sun Fire X2270 M2 Server - Version Not Applicable to Not Applicable [Release N/A]
Information in this document applies to any platform.
Goal
How to Replace Sun Fire X2270 M2 Memory DIMM.
Solution
DISPATCH INSTRUCTIONS
- WHAT SKILLS DOES THE ENGINEER NEED:
- TIME ESTIMATE: 30 minutes
- TASK COMPLEXITY: 0
WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :
A data backup is not a pre-requisite but is a wise precaution.
The customer should conduct an orderly software system shutdown.
Then power down the system and disconnect the Power Cord.
FIELD ENGINEER INSTRUCTIONS:
- PROBLEM OVERVIEW: How to remove and replace a DIMM
- WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE
RESOLUTION ACTIVITY?:
- WHAT ACTION DOES THE ENGINEER NEED TO TAKE:
1 Prepare the server for service. See How to Prepare for Service.
2 Remove the air duct. See How to Remove the Air Duct.
3 Locate the DIMM socket in which you want to install or replace a memory module. See DIMM Slot Designations.
4 Eject the DIMM from the slot by simultaneously pressing down on the ejector levers at both ends of the DIMM socket.
This action releases the DIMM from the slot.
5 To remove the DIMM, lift it up and out of the socket.
6 Install the replacement DIMM ensuring that the DIMM is properly rotated to allow the "key" to sit correctly.
7 Replace the air duct and replace the top cover.
8 Return the server to operation. See How to Prepare for Operation
OBTAIN CUSTOMER ACCEPTANCE
- WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO
AN OPERATIONAL STATE:
Power on and boot the system.
PARTS NOTE:
REFERENCE INFORMATION:
How to Remove a DIMM
How to Install a DIMM
Error Correction and Parity
DIMM Population Rules
Sun Fire X2270 M2 Server Service Manual