Sun Microsystems, Inc.  Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-71-1311780.1
Update Date:2016-01-20
Keywords:

Solution Type  Technical Instruction Sure

Solution  1311780.1 :   CAM - How to Remove and Replace Midrange Disk CSM100 Power Supply Unit:ATR:2365:1  


Related Items
  • Sun Storage Flexline 380 Array
  •  
  • Sun Storage 6580 Array
  •  
  • Sun Storage Flexline 240 Array
  •  
  • Sun Storage B280 Array
  •  
  • Sun Storage D240 (STK) Array
  •  
  • Sun Storage 6540 Array
  •  
  • Sun Storage Flexline 280 Array
  •  
  • Sun Storage 6130 Array
  •  
  • Sun Storage 6780 Array
  •  
  • Sun Storage D280 Disk Subsystem
  •  
  • Sun Storage 6140 Array
  •  
Related Categories
  • PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: DISK-CAP VCAP
  •  




In this Document
Goal
Solution


Oracle Confidential INTERNAL - Do not distribute to customer (OracleConfidential).
Reason: FRU CAP

Applies to:

Sun Storage Flexline 380 Array - Version Not Applicable to Not Applicable [Release N/A]
Sun Storage 6780 Array - Version Not Applicable to Not Applicable [Release N/A]
Sun Storage D240 (STK) Array - Version Not Applicable to Not Applicable [Release N/A]
Sun Storage 6140 Array - Version Not Applicable to Not Applicable [Release N/A]
Sun Storage 6580 Array - Version Not Applicable to Not Applicable [Release N/A]
Information in this document applies to any platform.

Goal

How to remove and replace a CSM100 Power Supply Unit in CAM.

Solution

DISPATCH INSTRUCTIONS
WHAT SKILLS DOES THE FIELD ENGINEER/ADMINISTRATOR NEED?:
Has gone through basic 2500/6000 Array Hardware Introduction
Common Array Manager

TIME ESTIMATE: 15 minutes

TASK COMPLEXITY: 1


FIELD ENGINEER/ADMINISTRATOR INSTRUCTIONS:

PROBLEM OVERVIEW: CSM100/FLA200/FLC200/FLA300 Power Supply has been identified as faulty.

WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :

WHAT ACTION DOES THE FIELD ENGINEER/ADMINISTRATOR NEED TO TAKE?:

NOTE: If ASR is enabled, it should be deactivated temporarily before servicing the equipment so that additional unnecessary Service Requests are not created.

DEACTIVATING ASR WITH CAM 6.10: ASR is automatically deactivated when you select "Reserve the tray for maintenance" in Service Advisor, and it is reactivated when you select "Release the tray from maintenance" in Service Advisor.

DEACTIVATING ASR WITH CAM 6.9 OR EARLIER: Before proceeding with the part replacement:

1. Log into CAM.
2. Go to "Storage Systems" -> [your arrayname] -> "Administration" -> "Array Health Monitoring".
3. Uncheck the box "Enable ASR for this array" under the section "Monitoring for This Array". If the box is already unchecked, there is no action required. Remember the status however, as it will matter in step 3 of REACTIVATING ASR WITH CAM 6.9 OR EARLIER below.
4. Click on "Save" if you have unchecked the box in step 3 above.


1. Log into CAM and open the service advisor.
2. Under the Power Supply Removal/Replacement, select the tray and power supply.
3. Follow the Power Supply Replacement Instructions therein.

OBTAIN CUSTOMER ACCEPTANCE

WHAT ACTION DOES THE FIELD ENGINEER/ADMINISTRATOR NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE?:
1. Verify That no critical faults exist on the system

REACTIVATING ASR with CAM 6.10: ASR is automatically deactivated when you select "Reserve the tray for maintenance" in Service Advisor, and it is reactivated when you select "Release the tray from maintenance" in Service Advisor. If ASR was not enabled before beginning this procedure, selecting "Release the tray from maintenance" will not activate it.

REACTIVATING ASR WITH CAM 6.9 OR EARLIER: After proceeding with the part replacement:

1. Log into CAM.
2. Go to "Storage Systems" -> [your arrayname] -> "Administration" -> "Array Health Monitoring".
3. Check the box "Enable ASR for this array" under the section "Monitoring for This Array". Do this ONLY if you unchecked the box in step 3 of DEACTIVATING ASR WITH CAM 6.9 OR EARLIER. If you found the box was unchecked, leave it unchecked now.
4. Click on "Save" if you have checked the box to reactivate ASR.


PARTS NOTE:

REFERENCE INFORMATION: The Service Advisor in CAM

NOTE: If the service advisor is not available, you may download or review a soft copy internally at: http://pts-storage.us.oracle.com/products/CAM/SA.html


Attachments
This solution has no attachment
  Copyright © 2018 Oracle, Inc.  All rights reserved.
 Feedback