How to Replace a V445 Fan Assembly:ATR:1119:0
Related Categories |
- PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: SPARC-CAP VCAP
|
In this Document
Applies to:
Sun Fire V445 Server - Version Not Applicable and later
Information in this document applies to any platform.
Goal
How to remove and replace a Sun Fire V445 Fan Assy
Solution
DISPATCH INSTRUCTIONS
WHAT SKILLS DOES THE FIELD ENGINEER/ADMINISTRATOR NEED?:
No specific skills required
TIME ESTIMATE: 15 Minutes
TASK COMPLEXITY: 0
FIELD ENGINEER/ADMINISTRATOR INSTRUCTIONS:
PROBLEM OVERVIEW:
Faulty Fan
WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :
A data backup is not a prerequisite but is a wise precaution.
The customer is not required to perform a system shutdown.
WHAT ACTION DOES THE ENGINEER NEED TO TAKE:
1. Determine which fan tray needs to be removed
2. Open the appropriate fan tray door
3. Release the fan tray from its bracket pulling the two green release pins up
4. Grasp the fan tray by its release pins and pull the fan tray up and out of the system
5. Insert the new fan tray
6. Confirm that the new fan tray is working
The fay tray indicator should be green
7. Close the fan tray door
WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:
Check Fan tray LEDs
PARTS NOTE:
REFERENCE INFORMATION:
Sun Fire V445 Server Service Manual.