1308610.1
:
How Remove and Replace a Starcat Power Supply Unit:ATR:501:2
Related Items |
- Sun Fire E25K Server
- Sun Fire 12K Server
- Sun Fire 15K Server
- Sun Fire E20K Server
|
Related Categories |
- PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: SPARC-CAP VCAP
|
In this Document
Oracle Confidential PARTNER - Available to partners (SUN).
Reason: FRU CAP
Applies to:
Sun Fire 12K Server - Version Not Applicable and later
Sun Fire 15K Server - Version Not Applicable and later
Sun Fire E20K Server - Version Not Applicable and later
Sun Fire E25K Server - Version Not Applicable and later
Information in this document applies to any platform.
Goal
How remove and replace a Starcat PSU
Solution
CAP PROBLEM OVERVIEW: Replace Power Supply Unit (PSU)
DISPATCH INSTRUCTIONS
WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?)
Starcat Training
Knowledge of SMS commands
FIELD ENGINEER INSTRUCTIONS
WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :
This type of FRU is Hot swappable.
WHAT ACTION DOES THE ENGINEER NEED TO TAKE:
From the Main SC:
SC> showenvironment
SC> poweroff ps#
PS0: powered off
Perform the physical replacement
The PSU can be removed when the "ok to remove" LED is lit.
SC> poweron ps#
PS0: powered on
Check to ensure power supply is ok.
SC> showenvironment -p powers
OBTAIN CUSTOMER ACCEPTANCE
WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:
None.
PARTS NOTE:
This Power Supply weighs 19.5 Kilograms (43 Lbs).
Front Power Supplies are labeled PS0, PS1, and PS2 from right to left.
Rear Power Supplies are labeled PS3, PS4, and PS5 from right to left.
REFERENCE INFORMATION:
E25K/E20K Service Manual: http://download.oracle.com/docs/cd/E19065-01/servers.e25k/index.html