Solution  1302088.1 :   M8000 M9000 How to Replace a Fan Tray:ATR:621:2  


Related Items
  • Sun SPARC Enterprise M9000-64 Server
  •  
  • Sun SPARC Enterprise M9000-32 Server
  •  
  • Sun SPARC Enterprise M8000 Server
  •  
Related Categories
  • PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: SPARC-CAP VCAP
  •  




In this Document
  Goal
  Solution


Oracle Confidential (INTERNAL). Do not distribute to customers
Reason: FRU CAP

Applies to:

Sun SPARC Enterprise M9000-32 Server - Version: Not Applicable and later   [Release: N/A and later ]
Sun SPARC Enterprise M9000-64 Server - Version: Not Applicable and later    [Release: N/A and later]
Sun SPARC Enterprise M8000 Server - Version: Not Applicable and later    [Release: N/A and later]
Information in this document applies to any platform.

Goal

CAP PROBLEM OVERVIEW: M8000 M9000 Fan Tray
********************************************************************************
To report errors or request improvements on this procedure,
please go to http://support.us.oracle.com and put a comment on Doc ID: 1302088.1
********************************************************************************

Solution

DISPATCH INSTRUCTIONS

WHAT SKILLS DOES THE ENGINEER NEED:(IS A SITE ENGINEER AVAILABLE?)
The engineer should be M8000 M9000 trained

TASK COMPLEXITY: 2

Time Estimate: 120 minutes

FIELD ENGINEER INSTRUCTIONS

WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :

A data backup is not a pre-requisite but is a wise precaution.
The customer is not required to perform a system shutdown unless opting for 'Cold Replacement'

WHAT ACTION DOES THE ENGINEER NEED TO TAKE:

Active Replacement:

1) Log in to XSCF and execute the replacefru command. ( Must have fieldeng permissions )
2) Select FAN Unit
3) Select the number of the faulted FAN Unit.
4) Perform the operation according to the instructions displayed in the maintenance menu.
5) Once the replacement is complete check the status to ensure no further fru's are in degraded or faulted status.
XSCF> showhardconf -M
XSCF> showstatus

Cold Replacement:
1) Change the mode switch setting on the operator panel from Locked to Service.
2) Following either method a) or b) shutdown and power off all domains.
a) Press and hold the POWER switch on the operator panel for at least four seconds.
b) Log in to XSCF and run the poweroff -a command.
3) Confirm that the power-off processing is completed by confirming that the
POWER LED (green) on the operator panel is off.
Note: On a M9000 with an expansion cabinet the base cabinet should be switched off first then the expansion cabinet.
4) Switch off all main line switches for the AC section (ACS) in the power supply system.
Note: On a M9000 with an expansion cabinet the expansion cabinet should be switched on first then the base cabinet.
5) Once the replacement is complete switch on all main line switches for the AC section (ACS) in the power supply system.
6) Once the replacement is complete check the status to ensure no further fru's are in degraded or faulted status.
XSCF> showhardconf -M
XSCF> showstatus


OBTAIN CUSTOMER ACCEPTANCE

WHAT ACTION DOES THE CUSTOMER NEED TO TAKE TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:
No additional work is required of the customer

PARTS NOTE:
Caution – Do not forcibly push the FAN unit when inserting it, even if it is not
moving smoothly. If the FAN unit is forcibly inserted despite the presence of any
obstruction in a slot or any problem with a connector pin, serious damage may
result.

REFERENCE INFORMATION: