Solution  1299308.1 :   How to Remove and Replace a SPARC T3-1 Fan Module:ATR:2569:0  


Related Items
  • SPARC T3-1
  •  
Related Categories
  • PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: SPARC-CAP VCAP
  •  




In this Document
Goal
Solution


Applies to:

SPARC T3-1 - Version Not Applicable and later
Information in this document applies to any platform.

Goal

Service SPARC T3-1 Fan Module

Solution

DISPATCH INSTRUCTIONS

WHAT SKILLS ARE REQUIRED:
No special skills required, Customer Replaceable Unit (CRU) procedure

Time Estimate: 60 minutes

Task Complexity: 0

REMOVAL/REPLACEMENT INSTRUCTIONS

PROBLEM OVERVIEW: Fan failure

WHAT STATE SHOULD THE SYSTEM BE IN TO BE READY TO PERFORM THE RESOLUTION ACTIVITY? :

DAMAGE ALERT: Perform a visual inspection of the replacement part to make sure that there are no damaged components, connectors, bent pins, damaged packages during shipping, etc. If the part is damaged, don't install it into the system, order a new part. Handle with caution and package carefully the return part to avoid any damages during shipping.


Take ESD Precautions

WHAT ACTIONS ARE REQUIRED:

A. Locate a Faulty Fan Module

1. Check the front or rear panel System Fault LED.

* A fan fault will cause the System Fault LED (on front and rear of server) as well as a Fan Fault LED in the array of fan status LEDs to be lighted.

2. Extend the server to the maintenance position.

3. Release the two fan compartment door latches and swing the door open.

4. If the color of a Fan Fault LED is amber, replace the corresponding fan module.

B. Remove a Fan Module

1. Extend the server to the maintenance position.

2. Release the two fan compartment door latches and swing the door open.

3. Check the fan status LEDs to determine which fan module or modules need to be replaced.

* An amber LED identifies the faulty fan module.

4. To remove a fan module, grasp the pull tab, pull the module toward the front of the system, and then lift it up and out of the fan module compartment.

5. Check to be certain adjacent fan modules are still fully seated.

* You can do this by pressing down on the top of the neighboring fan modules.

C. Install a Fan Module

1. Repeat steps B.1 and B.2.

2. Align the connector pins on the base of the new fan module with the connector on the fan module board and lower the module straight down into the slot.

3. Press down on the top of the module until it is fully seated.

4. Check the following status LEDs to verify that the new fan is functioning.

* The fan module status LED associated with that fan module should be green.
* Both Service Required LEDs should be off.

5. Return the server to its operational position in the rack.

OBTAIN CUSTOMER ACCEPTANCE

WHAT ACTIONS ARE REQUIRED TO RETURN THE SYSTEM TO AN OPERATIONAL STATE:

Verify functionality, no service LEDs or messages

PARTS NOTE:

https://support.oracle.com/handbook_private/Systems/SPARC_T3_1/components.html#Fan

REFERENCE INFORMATION: SPARC T3-1 Service Manual, p/n E21416