Goal

What are the AC Power Distribution Requirements for SL8500 Libraries?

How to determine the type of PDU installed.

Solution

Reference the description below for general information on the PDU used in the SL8500. To determine the type of PDU installed verify with the facilities manager the power requirements at your facility and match it with the descriptions below.

Another option is to obtain the part number from the back of the PDU which is located behind the rear library doors on the bottom right hand side. The part number tag is on the back of the PDU. Add the PDU part number and/or description to the service ticket.

Description:

Power for the SL8500 library must be supplied through directly wiring the Power Distribution Unit (PDU) connectors to the customer-supplied circuit breaker. AC power for the library is routed through power distribution units (PDUs) to +48 VDC power supplies.

NOTE: Power cabling must be done by a licensed electrician. Torque specifications and use of conduit are required. Refer to the System Assurance Guide, PN MT9229, or Installation Manual, PN 96138, for details.

The four power options for SL8500 libraries are:

1. 200 - 240 VAC, single phase, 24A, 50 - 60 HZ (up to three per PDU)

    PN_419641701 or 7056325 or 7325580

2. 200 - 240 VAC, line-to-line, three phase, 40A, 50 - 60 HZ, Delta (generally used in the U.S.)

    PN_419641901 or 7056347 or 7325590

3. 200 - 240 VAC, line-to-neutral, three phase, 24A, 50 - 60 HZ, WYE (generally used in Europe)

    PN_419641801 or 7056634 or 7325585

4. 200 - 240 VAC, line-to-neutral, three phase, 24A, 50 - 60 HZ, SUVA (wye)

    Discontinued

 

 