Sun Microsystems, Inc.  Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-79-2309633.1
Update Date:2018-03-23
Keywords:

Solution Type  Predictive Self-Healing Sure

Solution  2309633.1 :   Oracle SuperCluster M8: Supported Firmware bundles  


Related Items
  • Oracle SuperCluster M8 Hardware
  •  
Related Categories
  • PLA-Support>Sun Systems>SPARC>Enterprise>SN-SPARC: SuperCluster-Mx
  •  


This is the companion document to the Oracle SuperCluster M8 EIS checklist.
This document lists the FW version bundles at RR and for each QFSDP.

Best practices at installation time (when running EIS checklist) is to install the latest firmware bundle listed (the latest QFSDP).

In this Document
Purpose
Scope
Details


Oracle Confidential PARTNER - Available to partners (SUN).
Reason: Initial distribution

Applies to:

Oracle SuperCluster M8 Hardware - Version All Versions to All Versions [Release All Releases]
Information in this document applies to any platform.

Purpose

This is the companion document to the Oracle SuperCluster M8 EIS checklist.
This document lists the FW version bundles at RR and for each QFSDP.
Best practices at installation time (when running EIS checklist) is to install the latest firmware bundle listed (the latest QFSDP ... on top of the following table).

Scope

 Intended audience : field engineers performing Oracle SuperCluster M8 EIS checklist.

Details

 

 

 Supported FW bundles for Oracle SuperCluster M8

 RR/QFSDP

bundles

 M8 FW/HW Programmables

 ZS5-ES

(AK.../ILOM/BIOS)

 Exadata cells Exadata Storage Cell CX-3 IB cards

 NM2

Infiniband switches

Fortville Fcode

10Gb NIC

M8 CX-3

IB cards

 PDUs  Cisco 91308

Build 2.5.12

Sysfw 9.8.0.d

Note: No changes FPGA

 

 

AK: 2013.06.05.7.14,1-1.1

CX3 IB Firmware revision : 2.11.1280

 

 18.1.4.0.0.180125.3

2.35.5532

2.2.7-1

3.9 2.11.1280  2.0.7   7.0(3)I5

RR

(build 2.5.10)

ARU 21725530

 

Sysfw 9.8.0.c

 

AK: 2013.06.05.7.8,1-1.1

IB Firmware revision : 2.11.1280

 

18.1.1.0.0 2.35.5532 2.2.6-2

 

3.7

 

 

2.11.1280

 

2.0.7 7.0(3)I5

Policy:

- Do NOT downgrade any FW if factory has installed a more recent version than the one mentioned in the latest QFSDP. (unless explicitly advised otherwise.)