Asset ID: |
1-79-1555591.1 |
Update Date: | 2017-08-23 |
Keywords: | |
Solution Type
Predictive Self-Healing Sure
Solution
1555591.1
:
PDU Thresholds for Exalogic X2-2 / X3-2 / X4-2 / X5-2 Racks [Eighth / Quarter / Half / Full]
Related Items |
- Exalogic Elastic Cloud X4-2 Hardware
- Exalogic Elastic Cloud X5-2 Hardware
- Oracle Exalogic Elastic Cloud X2-2 Hardware
- Oracle Exalogic Elastic Cloud Software
- Exalogic Elastic Cloud X3-2 Hardware
|
Related Categories |
- PLA-Support>Eng Systems>Exalogic/OVCA>Oracle Exalogic>MW: Exalogic Core
|
In this Document
Created from <SR 3-7076899851>
Applies to:
Oracle Exalogic Elastic Cloud X2-2 Hardware
Exalogic Elastic Cloud X3-2 Hardware
Exalogic Elastic Cloud X4-2 Hardware
Exalogic Elastic Cloud X5-2 Hardware
Oracle Exalogic Elastic Cloud Software
Oracle Solaris on x86-64 (64-bit)
Linux x86-64
Oracle Virtual Server(x86-64)
Purpose
PDU Thresholds (Pre-warning and Alarm) for Exalogic X2-2 / X3-2 / X4-2 Racks [Eighth / Quarter / Half / Full]
Details
Exalogic X2-2 - Eighth Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
7 |
6 |
M1-2 |
M1-1 |
9 |
8 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
9 |
8 |
M1-2 |
M1-3 |
12 |
11 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
5 |
4 |
M1-3 |
M1-2 |
9 |
1 |
M1-2 |
M1-1 |
13 |
9 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
2 |
0 |
M1-2 |
M2-1 |
2 |
2 |
M1-1 |
|
|
|
|
M1-3 |
5 |
4 |
M2-3 |
M1-2 |
8 |
1 |
M2-2 |
M1-1 |
11 |
8 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
6 |
6 |
M1-3 |
M1-2 |
12 |
2 |
M1-2 |
M1-1 |
16 |
12 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
3 |
0 |
M1-2 |
M2-1 |
3 |
3 |
M1-1 |
|
|
|
|
M1-3 |
6 |
6 |
M2-3 |
M1-2 |
10 |
2 |
M2-2 |
M1-1 |
15 |
10 |
M2-1 |
Exalogic X2-2 - Quarter Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
7 |
7 |
M1-2 |
M1-1 |
17 |
15 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
9 |
9 |
M1-2 |
M1-3 |
21 |
19 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
8 |
5 |
M1-3 |
M1-2 |
16 |
4 |
M1-2 |
M1-1 |
17 |
13 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
2 |
0 |
M1-2 |
M2-1 |
2 |
2 |
M1-1 |
|
|
|
|
M1-3 |
8 |
5 |
M2-3 |
M1-2 |
14 |
4 |
M2-2 |
M1-1 |
15 |
11 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
11 |
7 |
M1-3 |
M1-2 |
20 |
6 |
M1-2 |
M1-1 |
21 |
17 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
3 |
0 |
M1-2 |
M2-1 |
3 |
3 |
M1-1 |
|
|
|
|
M1-3 |
11 |
7 |
M2-3 |
M1-2 |
18 |
6 |
M2-2 |
M1-1 |
19 |
15 |
M2-1 |
Exalogic X2-2 - Half Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
17 |
16 |
M1-2 |
M1-1 |
23 |
21 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
22 |
20 |
M1-2 |
M1-3 |
24 |
24 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
19 |
10 |
M1-3 |
M1-2 |
25 |
10 |
M1-2 |
M1-1 |
26 |
17 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
6 |
0 |
M1-2 |
M2-1 |
6 |
6 |
M1-1 |
|
|
|
|
M1-3 |
19 |
10 |
M2-3 |
M1-2 |
20 |
10 |
M2-2 |
M1-1 |
21 |
12 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
24 |
13 |
M1-3 |
M1-2 |
32 |
12 |
M1-2 |
M1-1 |
33 |
21 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
7 |
0 |
M1-2 |
M2-1 |
7 |
8 |
M1-1 |
|
|
|
|
M1-3 |
24 |
13 |
M2-3 |
M1-2 |
26 |
12 |
M2-2 |
M1-1 |
26 |
15 |
M2-1 |
Exalogic X2-2 - Full Rack
Single Phase
Pre-Warning Thresholds - Single Phase 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
22kVA |
M1-3 |
23 |
21 |
M1-1 |
M1-2 |
23 |
21 |
M1-2 |
M1-1 |
24 |
21 |
M1-3 |
Alarm Thresholds - Single Phase 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
22kVA |
M1-3 |
29 |
27 |
M1-1 |
M1-2 |
29 |
27 |
M1-2 |
M1-3 |
30 |
27 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
24kVA |
M2-3 |
21 |
11 |
M1-3 |
M2-2 |
20 |
11 |
M1-2 |
M2-1 |
20 |
10 |
M1-1 |
|
|
|
|
M1-3 |
19 |
10 |
M2-3 |
M1-2 |
20 |
10 |
M2-2 |
M1-1 |
20 |
12 |
M2-1 |
Alarm Thresholds - Three Phase 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
24kVA |
M2-3 |
27 |
15 |
M1-3 |
M1-2 |
25 |
15 |
M1-2 |
M1-1 |
25 |
13 |
M1-1 |
|
|
|
|
M1-3 |
24 |
13 |
M2-3 |
M1-2 |
26 |
13 |
M2-2 |
M1-1 |
26 |
15 |
M2-1 |
Exalogic X3-2 - Eighth Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
7 |
6 |
M1-2 |
M1-1 |
9 |
8 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
9 |
8 |
M1-2 |
M1-3 |
11 |
10 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
5 |
4 |
M1-3 |
M1-2 |
9 |
1 |
M1-2 |
M1-1 |
12 |
9 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
2 |
0 |
M1-2 |
M2-1 |
2 |
2 |
M1-1 |
|
|
|
|
M1-3 |
4 |
4 |
M2-3 |
M1-2 |
8 |
1 |
M2-2 |
M1-1 |
10 |
7 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
6 |
6 |
M1-3 |
M1-2 |
12 |
2 |
M1-2 |
M1-1 |
16 |
12 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
3 |
0 |
M1-2 |
M2-1 |
3 |
3 |
M1-1 |
|
|
|
|
M1-3 |
6 |
6 |
M2-3 |
M1-2 |
10 |
2 |
M2-2 |
M1-1 |
13 |
10 |
M2-1 |
Exalogic X3-2 - Quarter Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
7 |
6 |
M1-2 |
M1-1 |
16 |
15 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
9 |
8 |
M1-2 |
M1-3 |
21 |
19 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
8 |
4 |
M1-3 |
M1-2 |
16 |
4 |
M1-2 |
M1-1 |
16 |
12 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
2 |
0 |
M1-2 |
M2-1 |
2 |
2 |
M1-1 |
|
|
|
|
M1-3 |
7 |
4 |
M2-3 |
M1-2 |
14 |
4 |
M2-2 |
M1-1 |
14 |
11 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
10 |
6 |
M1-3 |
M1-2 |
20 |
6 |
M1-2 |
M1-1 |
20 |
16 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
3 |
0 |
M1-2 |
M2-1 |
3 |
3 |
M1-1 |
|
|
|
|
M1-3 |
10 |
6 |
M2-3 |
M1-2 |
18 |
6 |
M2-2 |
M1-1 |
18 |
14 |
M2-1 |
Exalogic X3-2 - Half Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA and 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
16 |
15 |
M1-2 |
M1-1 |
22 |
20 |
M1-3 |
22kVA |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
16 |
15 |
M1-2 |
M1-1 |
22 |
20 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA and 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
21 |
19 |
M1-2 |
M1-3 |
24 |
24 |
M1-3 |
22kVA |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
21 |
19 |
M1-2 |
M1-1 |
28 |
26 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
18 |
10 |
M1-3 |
M1-2 |
24 |
10 |
M1-2 |
M1-1 |
24 |
16 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
5 |
0 |
M1-2 |
M2-1 |
5 |
6 |
M1-1 |
|
|
|
|
M1-3 |
17 |
10 |
M2-3 |
M1-2 |
19 |
10 |
M2-2 |
M1-1 |
19 |
11 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
23 |
12 |
M1-3 |
M1-2 |
31 |
12 |
M1-2 |
M1-1 |
31 |
21 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
7 |
0 |
M1-2 |
M2-1 |
7 |
7 |
M1-1 |
|
|
|
|
M1-3 |
22 |
12 |
M2-3 |
M1-2 |
25 |
12 |
M2-2 |
M1-1 |
24 |
15 |
M2-1 |
Exalogic X3-2 - Full Rack
Single Phase
Pre-Warning Thresholds - Single Phase 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
22kVA |
M1-3 |
22 |
20 |
M1-1 |
M1-2 |
22 |
20 |
M1-2 |
M1-1 |
22 |
20 |
M1-3 |
Alarm Thresholds - Single Phase 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
22kVA |
M1-3 |
28 |
25 |
M1-1 |
M1-2 |
28 |
26 |
M1-2 |
M1-3 |
28 |
26 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
24kVA |
M2-3 |
20 |
11 |
M1-3 |
M2-2 |
19 |
11 |
M1-2 |
M2-1 |
19 |
9 |
M1-1 |
|
|
|
|
M1-3 |
18 |
10 |
M2-3 |
M1-2 |
19 |
10 |
M2-2 |
M1-1 |
19 |
11 |
M2-1 |
Alarm Thresholds - Three Phase 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
24kVA |
M2-3 |
26 |
14 |
M1-3 |
M1-2 |
24 |
14 |
M1-2 |
M1-1 |
24 |
12 |
M1-1 |
|
|
|
|
M1-3 |
23 |
13 |
M2-3 |
M1-2 |
25 |
12 |
M2-2 |
M1-1 |
25 |
15 |
M2-1 |
Exalogic X4-2 - Eighth Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
8 |
8 |
M1-2 |
M1-1 |
10 |
9 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
11 |
10 |
M1-2 |
M1-3 |
13 |
12 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
6 |
6 |
M1-3 |
M1-2 |
11 |
1 |
M1-2 |
M1-1 |
15 |
11 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
2 |
0 |
M1-2 |
M2-1 |
2 |
3 |
M1-1 |
|
|
|
|
M1-3 |
5 |
6 |
M2-3 |
M1-2 |
9 |
1 |
M2-2 |
M1-1 |
13 |
9 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
8 |
7 |
M1-3 |
M1-2 |
14 |
2 |
M1-2 |
M1-1 |
19 |
14 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
4 |
0 |
M1-2 |
M2-1 |
4 |
4 |
M1-1 |
|
|
|
|
M1-3 |
7 |
7 |
M2-3 |
M1-2 |
12 |
2 |
M2-2 |
M1-1 |
16 |
11 |
M2-1 |
Exalogic X4-2 - Quarter Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
8 |
8 |
M1-2 |
M1-1 |
19 |
18 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
11 |
10 |
M1-2 |
M1-3 |
24 |
22 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
10 |
6 |
M1-3 |
M1-2 |
19 |
5 |
M1-2 |
M1-1 |
19 |
15 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
2 |
0 |
M1-2 |
M2-1 |
2 |
3 |
M1-1 |
|
|
|
|
M1-3 |
9 |
6 |
M2-3 |
M1-2 |
17 |
5 |
M2-2 |
M1-1 |
17 |
13 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
13 |
7 |
M1-3 |
M1-2 |
24 |
7 |
M1-2 |
M1-1 |
24 |
19 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
4 |
0 |
M1-2 |
M2-1 |
4 |
4 |
M1-1 |
|
|
|
|
M1-3 |
12 |
7 |
M2-3 |
M1-2 |
21 |
7 |
M2-2 |
M1-1 |
21 |
17 |
M2-1 |
Exalogic X4-2 - Half Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA and 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
22 |
20 |
M1-2 |
M1-1 |
24 |
22 |
M1-3 |
22kVA |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
22 |
20 |
M1-2 |
M1-1 |
24 |
22 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA and 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
24 |
24 |
M1-2 |
M1-3 |
24 |
24 |
M1-3 |
22kVA |
M1-3 |
0 |
0 |
M1-1 |
M1-2 |
28 |
25 |
M1-2 |
M1-1 |
31 |
28 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
22 |
12 |
M1-3 |
M1-2 |
29 |
11 |
M1-2 |
M1-1 |
30 |
20 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
6 |
0 |
M1-2 |
M2-1 |
6 |
7 |
M1-1 |
|
|
|
|
M1-3 |
21 |
12 |
M2-3 |
M1-2 |
23 |
11 |
M2-2 |
M1-1 |
23 |
13 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
28 |
15 |
M1-3 |
M1-2 |
37 |
15 |
M1-2 |
M1-1 |
37 |
21 |
M1-1 |
24kVA |
M2-3 |
0 |
0 |
M1-3 |
M2-2 |
8 |
0 |
M1-2 |
M2-1 |
8 |
9 |
M1-1 |
|
|
|
|
M1-3 |
27 |
15 |
M2-3 |
M1-2 |
29 |
15 |
M2-2 |
M1-1 |
29 |
17 |
M2-1 |
Exalogic X4-2 - Full Rack
Single Phase
Pre-Warning Thresholds - Single Phase 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
22kVA |
M1-3 |
26 |
24 |
M1-1 |
M1-2 |
27 |
25 |
M1-2 |
M1-1 |
27 |
24 |
M1-3 |
Alarm Thresholds - Single Phase 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
22kVA |
M1-3 |
33 |
30 |
M1-1 |
M1-2 |
34 |
31 |
M1-2 |
M1-3 |
34 |
31 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
24kVA |
M2-3 |
24 |
13 |
M1-3 |
M2-2 |
23 |
13 |
M1-2 |
M2-1 |
23 |
11 |
M1-1 |
|
|
|
|
M1-3 |
22 |
12 |
M2-3 |
M1-2 |
23 |
11 |
M2-2 |
M1-1 |
24 |
13 |
M2-1 |
Alarm Thresholds - Three Phase 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
24kVA |
M2-3 |
31 |
17 |
M1-3 |
M1-2 |
29 |
17 |
M1-2 |
M1-1 |
29 |
15 |
M1-1 |
|
|
|
|
M1-3 |
27 |
16 |
M2-3 |
M1-2 |
29 |
15 |
M2-2 |
M1-1 |
30 |
17 |
M2-1 |
Exalogic X5-2 - Eighth Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
10 |
10 |
M1-1 |
M1-2 |
4 |
4 |
M1-2 |
M1-1 |
15 |
14 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
14 |
12 |
M1-1 |
M1-2 |
6 |
5 |
M1-2 |
M1-3 |
19 |
18 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
14 |
13 |
M1-3 |
M1-2 |
13 |
2 |
M1-2 |
M1-1 |
24 |
12 |
M1-1 |
24kVA |
M2-3 |
3 |
2 |
M1-3 |
M2-2 |
2 |
2 |
M1-2 |
M2-1 |
2 |
0 |
M1-1 |
|
|
|
|
M1-3 |
11 |
12 |
M2-3 |
M1-2 |
12 |
0 |
M2-2 |
M1-1 |
23 |
12 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
18 |
17 |
M1-3 |
M1-2 |
17 |
3 |
M1-2 |
M1-1 |
30 |
16 |
M1-1 |
24kVA |
M2-3 |
4 |
3 |
M1-3 |
M2-2 |
3 |
3 |
M1-2 |
M2-1 |
3 |
0 |
M1-1 |
|
|
|
|
M1-3 |
15 |
15 |
M2-3 |
M1-2 |
15 |
0 |
M2-2 |
M1-1 |
29 |
16 |
M2-1 |
Exalogic X5-2 - Quarter Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
10 |
10 |
M1-1 |
M1-2 |
8 |
7 |
M1-2 |
M1-1 |
24 |
23 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA or 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
M1-3 |
14 |
12 |
M1-1 |
M1-2 |
10 |
9 |
M1-2 |
M1-3 |
24 |
24 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
19 |
13 |
M1-3 |
M1-2 |
24 |
8 |
M1-2 |
M1-1 |
29 |
18 |
M1-1 |
24kVA |
M2-3 |
3 |
2 |
M1-3 |
M2-2 |
2 |
2 |
M1-2 |
M2-1 |
2 |
0 |
M1-1 |
|
|
|
|
M1-3 |
17 |
12 |
M2-3 |
M1-2 |
23 |
6 |
M2-2 |
M1-1 |
28 |
18 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
25 |
17 |
M1-3 |
M1-2 |
31 |
10 |
M1-2 |
M1-1 |
37 |
21 |
M1-1 |
24kVA |
M2-3 |
4 |
3 |
M1-3 |
M2-2 |
3 |
3 |
M1-2 |
M2-1 |
3 |
0 |
M1-1 |
|
|
|
|
M1-3 |
22 |
15 |
M2-3 |
M1-2 |
29 |
8 |
M2-2 |
M1-1 |
35 |
18 |
M2-1 |
Exalogic X5-2 - Half Rack
Single Phase
Pre-Warning Thresholds - Single Phase 15kVA and 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
20 |
18 |
M1-1 |
M1-2 |
24 |
22 |
M1-2 |
M1-1 |
24 |
23 |
M1-3 |
22kVA |
M1-3 |
20 |
18 |
M1-1 |
M1-2 |
24 |
22 |
M1-2 |
M1-1 |
24 |
23 |
M1-3 |
Alarm Thresholds - Single Phase 15kVA and 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
24 |
23 |
M1-1 |
M1-2 |
24 |
24 |
M1-2 |
M1-3 |
24 |
24 |
M1-3 |
22kVA |
M1-3 |
26 |
23 |
M1-1 |
M1-2 |
30 |
28 |
M1-2 |
M1-1 |
30 |
29 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
36 |
19 |
M1-3 |
M1-2 |
41 |
20 |
M1-2 |
M1-1 |
41 |
24 |
M1-1 |
24kVA |
M2-3 |
3 |
2 |
M1-3 |
M2-2 |
7 |
2 |
M1-2 |
M2-1 |
7 |
6 |
M1-1 |
|
|
|
|
M1-3 |
34 |
18 |
M2-3 |
M1-2 |
34 |
18 |
M2-2 |
M1-1 |
34 |
18 |
M2-1 |
Alarm Thresholds - Three Phase 15kVA and 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
15kVA |
M1-3 |
40 |
21 |
M1-3 |
M1-2 |
40 |
21 |
M1-2 |
M1-1 |
40 |
21 |
M1-1 |
24kVA |
M2-3 |
3 |
3 |
M1-3 |
M2-2 |
10 |
3 |
M1-2 |
M2-1 |
10 |
8 |
M1-1 |
|
|
|
|
M1-3 |
35 |
18 |
M2-3 |
M1-2 |
35 |
18 |
M2-2 |
M1-1 |
35 |
18 |
M2-1 |
Exalogic X5-2 - Full Rack
Single Phase
Pre-Warning Thresholds - Single Phase 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
22kVA |
M1-3 |
23 |
21 |
M1-1 |
M1-2 |
24 |
22 |
M1-2 |
M1-1 |
24 |
23 |
M1-3 |
Alarm Thresholds - Single Phase 22kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
22kVA |
M1-3 |
30 |
27 |
M1-1 |
M1-2 |
30 |
28 |
M1-2 |
M1-3 |
30 |
29 |
M1-3 |
Three Phase
Pre-Warning Thresholds - Three Phase 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
24kVA |
M2-3 |
34 |
18 |
M1-3 |
M2-2 |
34 |
18 |
M1-2 |
M2-1 |
34 |
18 |
M1-1 |
|
|
|
|
M1-3 |
34 |
18 |
M2-3 |
M1-2 |
34 |
18 |
M2-2 |
M1-1 |
34 |
18 |
M2-1 |
Alarm Thresholds - Three Phase 24kVA
PDU-A | Low Voltage | High Voltage | PDU-B |
24kVA |
M2-3 |
35 |
18 |
M1-3 |
M1-2 |
35 |
18 |
M1-2 |
M1-1 |
35 |
18 |
M1-1 |
|
|
|
|
M1-3 |
35 |
18 |
M2-3 |
M1-2 |
35 |
18 |
M2-2 |
M1-1 |
35 |
18 |
M2-1 |
Note:
For each phase of the input, to set Threshold Parameter Values in Volts:
Warning - Set the Voltage Warning level to the minimum nominal Line to Neutral voltage for the datacenter.
Alarm – Set the Voltage Alarm level to the minimum allowable operating Line to Neutral voltage for the datacenter.