Sun Microsystems, Inc.  Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-79-1555591.1
Update Date:2017-08-23
Keywords:

Solution Type  Predictive Self-Healing Sure

Solution  1555591.1 :   PDU Thresholds for Exalogic X2-2 / X3-2 / X4-2 / X5-2 Racks [Eighth / Quarter / Half / Full]  


Related Items
  • Exalogic Elastic Cloud X4-2 Hardware
  •  
  • Exalogic Elastic Cloud X5-2 Hardware
  •  
  • Oracle Exalogic Elastic Cloud X2-2 Hardware
  •  
  • Oracle Exalogic Elastic Cloud Software
  •  
  • Exalogic Elastic Cloud X3-2 Hardware
  •  
Related Categories
  • PLA-Support>Eng Systems>Exalogic/OVCA>Oracle Exalogic>MW: Exalogic Core
  •  




In this Document
Purpose
Details
 Exalogic X2-2 - Eighth Rack
 Single Phase
 Three Phase
 Exalogic X2-2 - Quarter Rack
 Single Phase
 Three Phase
 Exalogic X2-2 - Half Rack
 Single Phase
 Three Phase
 Exalogic X2-2 - Full Rack
 Single Phase
 Three Phase
 Exalogic X3-2 - Eighth Rack
 Single Phase
 Three Phase
 Exalogic X3-2 - Quarter Rack
 Single Phase
 Three Phase
 Exalogic X3-2 - Half Rack
 Single Phase
 Three Phase
 Exalogic X3-2 - Full Rack
 Single Phase
 Three Phase
 Exalogic X4-2 - Eighth Rack
 Single Phase
 Three Phase
 Exalogic X4-2 - Quarter Rack
 Single Phase
 Three Phase
 Exalogic X4-2 - Half Rack
 Single Phase
 Three Phase
 Exalogic X4-2 - Full Rack
 Single Phase
 Three Phase
 Exalogic X5-2 - Eighth Rack
 Single Phase
 Three Phase
 Exalogic X5-2 - Quarter Rack
 Single Phase
 Three Phase
 Exalogic X5-2 - Half Rack
 Single Phase
 Three Phase
 Exalogic X5-2 - Full Rack
 Single Phase
 Three Phase


Created from <SR 3-7076899851>

Applies to:

Oracle Exalogic Elastic Cloud X2-2 Hardware
Exalogic Elastic Cloud X3-2 Hardware
Exalogic Elastic Cloud X4-2 Hardware
Exalogic Elastic Cloud X5-2 Hardware
Oracle Exalogic Elastic Cloud Software
Oracle Solaris on x86-64 (64-bit)
Linux x86-64
Oracle Virtual Server(x86-64)

Purpose

PDU Thresholds (Pre-warning and Alarm) for Exalogic X2-2 / X3-2 / X4-2 Racks [Eighth / Quarter / Half / Full]

Details

Exalogic X2-2 - Eighth Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  7  6  M1-2
 M1-1  9  8  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  9  8  M1-2
 M1-3  12  11  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  5  4  M1-3
 M1-2  9  1  M1-2
 M1-1  13  9  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  2 0  M1-2
 M2-1  2 2  M1-1
       
M1-3 5 4 M2-3
M1-2 8 1 M2-2
M1-1 11 8 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  6  6  M1-3
 M1-2  12  2  M1-2
 M1-1  16  12  M1-1
24kVA
 M2-3 0 0  M1-3
 M2-2 3 0  M1-2
 M2-1 3 3  M1-1
       
M1-3 6 6 M2-3
M1-2 10 2 M2-2
M1-1 15 10 M2-1

Exalogic X2-2 - Quarter Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  7  7  M1-2
 M1-1  17  15  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  9  9  M1-2
 M1-3  21  19  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  8  5  M1-3
 M1-2  16  4  M1-2
 M1-1  17  13  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  2 0  M1-2
 M2-1  2 2  M1-1
       
M1-3 8 5 M2-3
M1-2 14 4 M2-2
M1-1 15 11 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  11  7  M1-3
 M1-2  20  6  M1-2
 M1-1  21  17  M1-1
24kVA
 M2-3 0 0  M1-3
 M2-2 3 0  M1-2
 M2-1 3 3  M1-1
       
M1-3 11 7 M2-3
M1-2 18 6 M2-2
M1-1 19 15 M2-1

Exalogic X2-2 - Half Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  17  16  M1-2
 M1-1  23  21  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  22  20  M1-2
 M1-3  24  24  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  19  10  M1-3
 M1-2  25  10  M1-2
 M1-1  26  17  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  6 0  M1-2
 M2-1  6 6  M1-1
       
M1-3 19 10 M2-3
M1-2 20 10 M2-2
M1-1 21 12 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  24  13  M1-3
 M1-2  32  12  M1-2
 M1-1  33  21  M1-1
24kVA
 M2-3 0 0  M1-3
 M2-2 7 0  M1-2
 M2-1 7 8  M1-1
       
M1-3 24 13 M2-3
M1-2 26 12 M2-2
M1-1 26 15 M2-1

Exalogic X2-2 - Full Rack

Single Phase

Pre-Warning Thresholds - Single Phase 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
22kVA
 M1-3  23  21  M1-1
 M1-2  23  21  M1-2
 M1-1  24  21  M1-3

Alarm Thresholds - Single Phase 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
22kVA
 M1-3  29  27  M1-1
 M1-2  29  27  M1-2
 M1-3  30  27  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
24kVA
 M2-3  21  11  M1-3
 M2-2  20  11  M1-2
 M2-1  20  10  M1-1
       
M1-3 19 10 M2-3
M1-2 20 10 M2-2
M1-1 20 12 M2-1

Alarm Thresholds - Three Phase 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
24kVA
 M2-3  27  15  M1-3
 M1-2  25  15  M1-2
 M1-1  25  13  M1-1
       
M1-3 24 13 M2-3
M1-2 26 13 M2-2
M1-1 26 15 M2-1

Exalogic X3-2 - Eighth Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  7  6  M1-2
 M1-1  9  8  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  9  8  M1-2
 M1-3  11  10  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  5  4  M1-3
 M1-2  9  1  M1-2
 M1-1  12  9  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  2 0  M1-2
 M2-1  2 2  M1-1
       
M1-3 4 4 M2-3
M1-2 8 1 M2-2
M1-1 10 7 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  6  6  M1-3
 M1-2  12  2  M1-2
 M1-1  16  12  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2 3 0  M1-2
 M2-1 3 3  M1-1
       
M1-3 6 6 M2-3
M1-2 10 2 M2-2
M1-1 13 10 M2-1

Exalogic X3-2 - Quarter Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  7  6  M1-2
 M1-1  16  15  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  9  8  M1-2
 M1-3  21  19  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  8  4  M1-3
 M1-2  16  4  M1-2
 M1-1  16  12  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  2 0  M1-2
 M2-1  2 2  M1-1
       
M1-3 7 4 M2-3
M1-2 14 4 M2-2
M1-1 14 11 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  10  6  M1-3
 M1-2  20  6  M1-2
 M1-1  20  16  M1-1
24kVA
 M2-3 0 0  M1-3
 M2-2 3 0  M1-2
 M2-1 3 3  M1-1
       
M1-3 10 6 M2-3
M1-2 18 6 M2-2
M1-1 18 14 M2-1

Exalogic X3-2 - Half Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA and 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  0  0  M1-1
 M1-2  16  15  M1-2
 M1-1  22  20  M1-3
22kVA
M1-3 0 0 M1-1
M1-2 16 15 M1-2
M1-1 22 20 M1-3

Alarm Thresholds - Single Phase 15kVA and 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  0  0  M1-1
 M1-2  21  19  M1-2
 M1-3  24  24  M1-3
22kVA
M1-3 0 0 M1-1
M1-2 21 19 M1-2
M1-1 28 26 M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  18  10  M1-3
 M1-2  24  10  M1-2
 M1-1  24  16  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  5 0  M1-2
 M2-1  5 6  M1-1
       
M1-3 17 10 M2-3
M1-2 19 10 M2-2
M1-1 19 11 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  23  12  M1-3
 M1-2  31  12  M1-2
 M1-1  31  21  M1-1
24kVA
 M2-3 0 0  M1-3
 M2-2 7 0  M1-2
 M2-1 7 7  M1-1
       
M1-3 22 12 M2-3
M1-2 25 12 M2-2
M1-1 24 15 M2-1

Exalogic X3-2 - Full Rack

Single Phase

Pre-Warning Thresholds - Single Phase 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
22kVA
 M1-3  22  20  M1-1
 M1-2  22  20  M1-2
 M1-1  22  20  M1-3

Alarm Thresholds - Single Phase 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
22kVA
 M1-3  28  25  M1-1
 M1-2  28  26  M1-2
 M1-3  28  26  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
24kVA
 M2-3  20  11  M1-3
 M2-2  19  11  M1-2
 M2-1  19  9  M1-1
       
M1-3 18 10 M2-3
M1-2 19 10 M2-2
M1-1 19 11 M2-1

Alarm Thresholds - Three Phase 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
24kVA
 M2-3  26  14  M1-3
 M1-2  24  14  M1-2
 M1-1  24  12  M1-1
       
M1-3 23 13 M2-3
M1-2 25 12 M2-2
M1-1 25 15 M2-1

Exalogic X4-2 - Eighth Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  8  8  M1-2
 M1-1  10  9  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  11  10  M1-2
 M1-3  13  12  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  6  6  M1-3
 M1-2  11  1  M1-2
 M1-1  15  11  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  2 0  M1-2
 M2-1  2 3  M1-1
       
M1-3 5 6 M2-3
M1-2 9 1 M2-2
M1-1 13 9 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  8  7  M1-3
 M1-2  14  2  M1-2
 M1-1  19  14  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2 4 0  M1-2
 M2-1 4 4  M1-1
       
M1-3 7 7 M2-3
M1-2 12 2 M2-2
M1-1 16 11 M2-1

Exalogic X4-2 - Quarter Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  8  8  M1-2
 M1-1  19  18  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  0  0  M1-1
 M1-2  11  10  M1-2
 M1-3  24  22  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  10  6  M1-3
 M1-2  19  5  M1-2
 M1-1  19  15  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  2 0  M1-2
 M2-1  2 3  M1-1
       
M1-3 9 6 M2-3
M1-2 17 5 M2-2
M1-1 17 13 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  13  7  M1-3
 M1-2  24  7  M1-2
 M1-1  24  19  M1-1
24kVA
 M2-3 0 0  M1-3
 M2-2 4 0  M1-2
 M2-1 4 4  M1-1
       
M1-3 12 7 M2-3
M1-2 21 7 M2-2
M1-1 21 17 M2-1

Exalogic X4-2 - Half Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA and 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  0  0  M1-1
 M1-2  22  20  M1-2
 M1-1  24  22  M1-3
22kVA
M1-3 0 0 M1-1
M1-2 22 20 M1-2
M1-1 24 22 M1-3

Alarm Thresholds - Single Phase 15kVA and 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  0  0  M1-1
 M1-2  24  24  M1-2
 M1-3  24  24  M1-3
22kVA
M1-3 0 0 M1-1
M1-2 28 25 M1-2
M1-1 31 28 M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  22  12  M1-3
 M1-2  29  11  M1-2
 M1-1  30  20  M1-1
24kVA
 M2-3  0 0  M1-3
 M2-2  6 0  M1-2
 M2-1  6 7  M1-1
       
M1-3 21 12 M2-3
M1-2 23 11 M2-2
M1-1 23 13 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  28  15  M1-3
 M1-2  37  15  M1-2
 M1-1  37  21  M1-1
24kVA
 M2-3 0 0  M1-3
 M2-2 8 0  M1-2
 M2-1 8 9  M1-1
       
M1-3 27 15 M2-3
M1-2 29 15 M2-2
M1-1 29 17 M2-1

Exalogic X4-2 - Full Rack

Single Phase

Pre-Warning Thresholds - Single Phase 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
22kVA
 M1-3  26  24  M1-1
 M1-2  27  25  M1-2
 M1-1  27  24  M1-3

Alarm Thresholds - Single Phase 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
22kVA
 M1-3  33  30  M1-1
 M1-2  34  31  M1-2
 M1-3  34  31  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
24kVA
 M2-3  24  13  M1-3
 M2-2  23  13  M1-2
 M2-1  23  11  M1-1
       
M1-3 22 12 M2-3
M1-2 23 11 M2-2
M1-1 24 13 M2-1

Alarm Thresholds - Three Phase 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
24kVA
 M2-3  31  17  M1-3
 M1-2  29  17  M1-2
 M1-1  29  15  M1-1
       
M1-3 27 16 M2-3
M1-2 29 15 M2-2
M1-1 30 17 M2-1

Exalogic X5-2 - Eighth Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  10  10  M1-1
 M1-2  4  4  M1-2
 M1-1  15  14  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  14  12  M1-1
 M1-2  6  5  M1-2
 M1-3  19  18  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  14  13  M1-3
 M1-2  13  2  M1-2
 M1-1  24  12  M1-1
24kVA
 M2-3  3 2  M1-3
 M2-2  2 2  M1-2
 M2-1  2 0  M1-1
       
M1-3 11 12 M2-3
M1-2 12 0 M2-2
M1-1 23 12 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  18  17  M1-3
 M1-2  17  3  M1-2
 M1-1  30  16  M1-1
24kVA
 M2-3 4 3  M1-3
 M2-2 3 3  M1-2
 M2-1 3 0  M1-1
       
M1-3 15 15 M2-3
M1-2 15 0 M2-2
M1-1 29 16 M2-1

Exalogic X5-2 - Quarter Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3 10 10  M1-1
 M1-2  8  7  M1-2
 M1-1  24  23  M1-3

Alarm Thresholds - Single Phase 15kVA or 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
 M1-3  14  12  M1-1
 M1-2  10  9  M1-2
 M1-3  24  24  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  19  13  M1-3
 M1-2  24  8  M1-2
 M1-1  29  18  M1-1
24kVA
 M2-3  3 2  M1-3
 M2-2  2 2  M1-2
 M2-1  2 0  M1-1
       
M1-3 17 12 M2-3
M1-2 23 6 M2-2
M1-1 28 18 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  25  17  M1-3
 M1-2  31  10  M1-2
 M1-1  37  21  M1-1
24kVA
 M2-3 4 3  M1-3
 M2-2 3 3  M1-2
 M2-1 3 0  M1-1
       
M1-3 22 15 M2-3
M1-2 29 8 M2-2
M1-1 35 18 M2-1

Exalogic X5-2 - Half Rack

Single Phase

Pre-Warning Thresholds - Single Phase 15kVA and 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  20 18  M1-1
 M1-2  24  22  M1-2
 M1-1  24  23  M1-3
22kVA
M1-3 20 18 M1-1
M1-2 24 22 M1-2
M1-1 24 23 M1-3

Alarm Thresholds - Single Phase 15kVA and 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  24  23  M1-1
 M1-2  24  24  M1-2
 M1-3  24  24  M1-3
22kVA
M1-3 26 23 M1-1
M1-2 30 28 M1-2
M1-1 30 29 M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  36  19  M1-3
 M1-2  41  20  M1-2
 M1-1  41  24  M1-1
24kVA
 M2-3  3 2  M1-3
 M2-2  7 2  M1-2
 M2-1  7 6  M1-1
       
M1-3 34 18 M2-3
M1-2 34 18 M2-2
M1-1 34 18 M2-1

Alarm Thresholds - Three Phase 15kVA and 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
15kVA
 M1-3  40  21  M1-3
 M1-2  40  21  M1-2
 M1-1  40  21  M1-1
24kVA
 M2-3 3 3  M1-3
 M2-2 10 3  M1-2
 M2-1 10 8  M1-1
       
M1-3 35 18 M2-3
M1-2 35 18 M2-2
M1-1 35 18 M2-1

Exalogic X5-2 - Full Rack

Single Phase

Pre-Warning Thresholds - Single Phase 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
22kVA
 M1-3  23  21  M1-1
 M1-2  24  22  M1-2
 M1-1  24  23  M1-3

Alarm Thresholds - Single Phase 22kVA

PDU-ALow VoltageHigh VoltagePDU-B
22kVA
 M1-3  30  27  M1-1
 M1-2  30  28  M1-2
 M1-3  30  29  M1-3

Three Phase

Pre-Warning Thresholds - Three Phase 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
24kVA
 M2-3  34  18  M1-3
 M2-2  34  18  M1-2
 M2-1  34  18  M1-1
       
M1-3 34 18 M2-3
M1-2 34 18 M2-2
M1-1 34 18 M2-1

Alarm Thresholds - Three Phase 24kVA

PDU-ALow VoltageHigh VoltagePDU-B
24kVA
 M2-3  35  18  M1-3
 M1-2  35  18  M1-2
 M1-1  35  18  M1-1
       
M1-3 35 18 M2-3
M1-2 35 18 M2-2
M1-1 35 18 M2-1

 

Note:

For each phase of the input, to set Threshold Parameter Values in Volts:

Warning - Set the Voltage Warning level to the minimum nominal Line to Neutral voltage for the datacenter.

Alarm – Set the Voltage Alarm level to the minimum allowable operating Line to Neutral voltage for the datacenter.

 


Attachments
This solution has no attachment
  Copyright © 2018 Oracle, Inc.  All rights reserved.
 Feedback