Asset ID: |
1-79-1534913.1 |
Update Date: | 2015-12-30 |
Keywords: | |
Solution Type
Predictive Self-Healing Sure
Solution
1534913.1
:
M10-env.temp.under - An undertemperature condition is detected by the inlet temperature sensor
Related Items |
- Fujitsu M10-4
- Fujitsu M10-1
- Fujitsu M10-4S
|
Related Categories |
- PLA-Support>Sun Systems>Sun_Other>Sun Collections>SN-OTH: Sun PSH
|
In this Document
Applies to:
Fujitsu M10-4S
Fujitsu M10-1
Fujitsu M10-4
SPARC
Purpose
Provide additional information for message ID: M10-env.temp.under
Fujitsu fault codes:
01911110, 11000033
Details
Type
- Hardware Fault
- env.temp.under
Severity
- Minor
Description
-
Fault due to an undertemperature condition detected by the inlet temperature sensor.
Automated Response
- No immediate action is taken. The platform administrator should check for the cause of the undertemperature condition.
Impact
- Nothing is deconfigured.
Indicted Hardware
- The suspect is the external environment.
Condensation may occur due to undertemperature conditions.
Additionally, there is risk of a system crash due to ASICs operating outside the intended temperature ranges (the timing of signals is different at low temperatures).
Suggested Action for System Administrator
- Refer to the following document for the latest procedures for displaying event content in preparation for submitting a service request and applying any post-repair actions that may be required.
PSH Procedural Article for Fujitsu M10 Diagnosis (Doc ID 1525156.1)

Attachments
This solution has no attachment