Sun Microsystems, Inc.  Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-72-2399905.1
Update Date:2018-05-21
Keywords:

Solution Type  Problem Resolution Sure

Solution  2399905.1 :   Eagle: UAM 0522-Frame Power Usage Reached LVL1  


Related Items
  • Oracle Communications EAGLE (Software)
  •  
Related Categories
  • PLA-Support>Sun Systems>CommsGBU>Global Signaling Solutions>SN-SND: Tekelec Eagle 5
  •  




In this Document
Symptoms
Changes
Cause
Solution


Created from <SR 3-17375804421>

Applies to:

Oracle Communications EAGLE (Software) - Version EAGLE 46.3 and later
Information in this document applies to any platform.

Symptoms

UAM 0522 - Frame power usage reached LVL1

======================================================================
0522 --Frame power usage reached LVL1
======================================================================
> rept-stat-trbl
 
Command Accepted - Processing
  eagle 18-04-27 10:31:59 GMT EAGLE 46.3.1.0.0-68.30.1
  Searching devices for alarms...
;
  eagle 18-04-27 10:31:59 GMT EAGLE 46.3.1.0.0-68.30.1
  SEQN UAM AL DEVICE ELEMENT TROUBLE TEXT
  -

  -

  -
  5849.0522 * FRAME EF03 Frame power usage reached LVL1 >>>>>>>>>>>>>> Power Alarm for EF03
  -
  -

  -
  Command Completed.
======================================================================



Changes

 

Cause

The maximum calculated power for a frame is based on the cards that are populated in the system, and includes a fan tray assembly for every shelf (the system cannot detect the presence or absence of a fan tray, and assumes presence for the calculation).
These values are typically much higher than the actual power being drawn; the values cannot be used as a gauge of the actual power consumption of the EAGLE.

--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
  eagle 18-04-27 10:35:27 GMT EAGLE 46.3.1.0.0-68.30.1
  
  Power Threshold Power Consumption
  Frame (Amps) (Watts) (Amps) (Watts)
  ----- ----------------- -----------------
  CF00 45 1800 35.70 1428
  EF00 45 1800 34.00 1360
  EF01 45 1800 33.66 1346
  EF02 45 1800 35.20 1408
  EF03 45 1800 42.49 1700 >>>>> The Power Threshold in Amps is Set to 45 and the EF03 power is reaching 42.49.
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------


This means the power Consumption is reaching more than 90% (LVL1) of the threshold value, and hence we are observing the alarm.
 

Solution

1. A lot of non-provisioned cards where inserted in frame EF03. It is advised to remove those cards from system.

2. If the cards are to be used soon, we only have the option of increasing the power threshold. Use the following command to increase the power threshold from 45 to 50.
  

  chg-frm-pwr: frm=ef03:thrshld=50


43Amps will be 86% of 50Amps threshold and is less than the 90% Level1 threshold. The alarm will be cleared this way.

Issue resolved after increasing power threshold.


Attachments
This solution has no attachment
  Copyright © 2018 Oracle, Inc.  All rights reserved.