UAM 0302 - Cooling Fan Failure
Related Items |
- Oracle Communications EAGLE (Hardware)
|
Related Categories |
- PLA-Support>Sun Systems>CommsGBU>Global Signaling Solutions>SN-SND: Tekelec Eagle 5
|
In this Document
Created from <SR 3-15733522401>
Applies to:
Oracle Communications EAGLE (Hardware) - Version EAGLE 46.0 and later
Tekelec
Symptoms
UAM 0302 - Cooling Fan Failure
Changes
Cause
The LED status indicated second fan unit of fan assembly in shelf 1200 is faulty.
Please find below the LED status of each fan unit of each fan assembly.
Shelf Fan Controller LED FAN 1 LED FAN 2 LED FAN 3 LED
1100 GREEN GREEN GREEN GREEN
1200 GREEN GREEN RED GREEN
1300 GREEN GREEN GREEN GREEN
2100 GREEN GREEN GREEN GREEN
2200 GREEN GREEN GREEN GREEN
We swapped FAN unit 2 of fan assembly at shelf 1200 and FAN unit 2 of fan assembly at shelf 2200 and LED status was as below.
Shelf Fan Controller LED FAN 1 LED FAN 2 LED FAN 3 LED
1100 GREEN GREEN GREEN GREEN
1200 GREEN GREEN GREEN GREEN
1300 GREEN GREEN GREEN GREEN
2100 GREEN GREEN GREEN GREEN
2200 GREEN GREEN RED GREEN
This clearly confirms the FAN unit 2 of fan assembly at shelf 1200 is faulty and needs to be replaced.
Solution
Replace the faulty second fan unit of fan assembly in shelf 1200.