T10000d - FSC515B, The Reel Annular Area Sum Computed During Load Was Not Believable
Related Items |
- StorageTek T10000D Tape Drive
|
Related Categories |
- PLA-Support>Sun Systems>TAPE>Tape Hardware>SN-TP: Remote
|
In this Document
Created from <SR 3-17142282109>
Applies to:
StorageTek T10000D Tape Drive - Version All Versions to All Versions [Release All Releases]
Information in this document applies to any platform.
Symptoms
T10000D
Summary:The reel annular area sum computed during load was not believable.
Fault event description:The reel annular area sum computed during load was not believable.
receiver_id: SDP2-2.3.2
The reel annular area sum computed during load was not believable.
************* ADDITIONAL INFORMATION *************
*** Alarm Description ***
FSC(515B): The reel annular area sum computed during load was not believable.
The reel annular area sum computed during load was not believable.
Device Dmod: 57900400xxxx
Tray SN: 57900020xxxx
Device Model: T10000D
Trap Type: tapenewpermlog
Locator Text: ACS/LSM/Pnl/Drv: 0/0/0/0, Library: SL8500 : tdembud01test, Drive Location: 1,1,-1,1,4, Mfg S/N: 57900400xxxx, Tray S/N: 57900020xxxx
Changes
Cause
FSC Dictionary Description:
MODEL = T10000D
FSC = 515B
(FSC Match Found in Rev. 4.13)
FSC: 515B LOD_FSC_RADNUM_BAD
MIM Code: NONE
FRU: HARDWARE CONF: 50%
FRU: MEDIA CONF: 50%
Summary: |MEDIA |REEL SYSTEM |HEAD ACTUATOR |
Field Text:
The reel annular area sum computed during load was not believable.
Solution
Have Customer power cycle the tape drive.
Perform cleaning on drive.
Have Customer perform the test backup with known good tape and check for error.
Customer should inspect the media where the error occurred for any possible damage.