Sun Microsystems, Inc.  Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-72-2314302.1
Update Date:2017-10-05
Keywords:

Solution Type  Problem Resolution Sure

Solution  2314302.1 :   OKM/SL8500 - Discussion On Which OKM Servers Will Fit Into The SL8500 Accessory Rack  


Related Items
  • Oracle Key Manager
  •  
  • Sun StorageTek SL8500 Modular Library System
  •  
Related Categories
  • PLA-Support>Sun Systems>TAPE>Tape Hardware>SN-TP: STK T-Series Drive
  •  




In this Document
Symptoms
Cause
Solution


Applies to:

Sun StorageTek SL8500 Modular Library System - Version All Versions and later
Oracle Key Manager - Version 1.1.0 and later
Information in this document applies to any platform.

Symptoms

OKM and KMA discussion regarding which OKM servers will fit in the SL8500 Accessory Rack. The SL8500 has a feature to add four standard RETMA2 19-inch racks, Marketing PN_ XSL8500-RACK-Z-N, that are oriented vertically instead of horizontally. The latter generations of the OKM servers may not fit in the SL8500 Accessory Rack.

Cause

 OKM/KMA discussion regarding which OKM servers will fit in the SL8500 Accessory Racks.

Solution

SL8500 Accessory Rack And OKM

OKM considerations for the SL8500 accessory rack.

The SL8500 rack is physically 28 inches deep but it can only handle equipment that is up to 26 inches in length as you have to leave room for cables and air flow.
The T4 (28 inches) and T7 servers (29 inches) exceed this length and cannot be mounted in the SL8500 accessory rack.

 

The 4170 (27 inches) is technically too long for the rack according to the rack spec.

x2100 and x2200 servers are 25 inches long and will fit.