![]() | Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition | ||
|
|
![]() |
||||||||||||||||
Solution Type Problem Resolution Sure Solution 2314302.1 : OKM/SL8500 - Discussion On Which OKM Servers Will Fit Into The SL8500 Accessory Rack
In this Document
Applies to:Sun StorageTek SL8500 Modular Library System - Version All Versions and laterOracle Key Manager - Version 1.1.0 and later Information in this document applies to any platform. SymptomsOKM and KMA discussion regarding which OKM servers will fit in the SL8500 Accessory Rack. The SL8500 has a feature to add four standard RETMA2 19-inch racks, Marketing PN_ XSL8500-RACK-Z-N, that are oriented vertically instead of horizontally. The latter generations of the OKM servers may not fit in the SL8500 Accessory Rack. CauseOKM/KMA discussion regarding which OKM servers will fit in the SL8500 Accessory Racks. SolutionSL8500 Accessory Rack And OKM OKM considerations for the SL8500 accessory rack. The SL8500 rack is physically 28 inches deep but it can only handle equipment that is up to 26 inches in length as you have to leave room for cables and air flow.
The 4170 (27 inches) is technically too long for the rack according to the rack spec. x2100 and x2200 servers are 25 inches long and will fit. Attachments This solution has no attachment |
||||||||||||||||
|