Solution Type Problem Resolution Sure Solution 2268899.1 : SL3000 - AEM Terminators Missing, The Library Thinks the Door is Open and Removes Power From the Rail Power Supplies
In this Document
Oracle Confidential PARTNER - Available to partners (SUN). Applies to:Sun StorageTek SL3000 Modular Library System - Version All Versions and laterInformation in this document applies to any platform. Customer had me remove AEMs from their libraries and install CEMS with CAPs. Now, that we're finished, I realize that I don't have the AEM card terminators to put on the cables coming out of the Base module that the AEMs plugged into. Has anyone ever had to order these terminators before? Do you have the part number(s) for them? SymptomsSL3000 - AEM Terminators Missing, The Library Thinks the Door is Open and Removes Power From the Rail Power Supplies. CauseAEMs removed for SL3000 and replaced with CEMs. Solution419928802 CBL ASSY,AEM DOOR JUMPER Production You may need to order the jumpers via the NOPRT process. How to Order Parts Using the 'No Parts Process', NOPRT (Doc ID 1285688.1) If it is an emergency you should be able to cut and use crimp connectors to join the 2 wires together in each P507/P508 harness. Use the image below as a reference for the wires to be tied together. Attachments This solution has no attachment |
||||||||||||||||||
|