Solution  2152418.1 :   Enhanced PDU Shows Voltage Power Consumption Error Without Anything Connected  


Related Items
  • Exadata X5-2 Quarter Rack
  •  
Related Categories
  • PLA-Support>Sun Systems>x86>Engineered Systems HW>SN-x64: EXADATA
  •  




In this Document
Symptoms
Cause
Solution


Created from <SR 3-11363892678>

Applies to:

Exadata X5-2 Quarter Rack - Version All Versions and later
Information in this document applies to any platform.

Symptoms

 Enhanced PDU meter shows error for input

Example

PDU-A
Input0 : Current 2.91A/Voltage 1.0V  <<<<<<<<<<
Input1 : Current 1.78A/Voltage 227.5V 
Input2 : Current 0.00A/Voltage 0.0V  <<<<<<<<<<
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
PDU-B
Input0 : Current 0.00A/Voltage 0.0V  <<<<<<<<<<
Input1 : Current 1.96A/Voltage 232.8V
Input2 : Current 2.85A/Voltage 1.0V  <<<<<<<<<

See below Images

 

 PDU-A

 Error shows on PDU-A

 

 

PDU-B

Error shows on PDU-B

 

Issue : Current / Voltage showing zero and sometimes a non-zero value with the Voltage square in "RED" color and state with a red "X" when nothing is connected

Cause

 The phase connected to PDU plug is not correct

Solution

Verify that voltage being applied at the PDU plug is the correct phasing.
See the below picture for correct phase connection to PDU input Plug

 

Input to PDU Plug

 

Expected: Current and Voltage values should be ZERO '0' when there is no equipment connected and the Voltage square should not be "RED" and the state should be a green tick.

NOTE : To check PDU Plug Phase connection, You may require data center electrician and field engineer.