Fuse Alarm in Control or Extension Shelf
Related Items |
- Oracle Communications EAGLE (Hardware)
|
Related Categories |
- PLA-Support>Sun Systems>CommsGBU>Global Signaling Solutions>SN-SND: Tekelec Eagle 5
- Tools>Type>Guide
|
In this Document
Created from <SR 3-11636142871>
Applies to:
Oracle Communications EAGLE (Hardware) - Version EAGLE 43.x and later
Information in this document applies to any platform.
Symptoms
One or more fuses send out alarms in main shelf.
Changes
Cause
Cause : There is two causes of this alarm..
- Its may be due to Hardware, such as a faulty fuse
- It may be a False Alarm, follow instructions from "Fake Fuse Alarms" (Doc ID 2076140.1) to confirm.
Solution
Troubleshooting Steps to clear the alarm:
- Verify the all slots (xx01 - xx18) of Shelf getting Fuse alarm and replace the Fuse
- Remove and replace Fuses of all slot (xx01 - xx18) one by one
- Reset the MASP Card
- Switch Over the MASP Card
- Reset the MDAL Card
- Replace the MDAL Card
- Remove the Backplane Alarm Cable and insert into other port of backplane and verify the status
- Replace the FUSE alarm cable
- Replace the FAP module component ( FAP_DB_A, FAP_JB, FAP_AB, FAP_DB_B ) with other Extension frame FAP Panel Component
- Remove and replace Fuses of all slot (xx01 - xx18) one by one
- Replace the FAP Panel Module.