Solution Type Problem Resolution Sure Solution 2110691.1 : SL150 - Library Not Scanning Expansion CAP
In this Document
Created from <SR 3-12051577954> Applies to:StorageTek SL150 Modular Tape Library - Version All Versions to All Versions [Release All Releases]Information in this document applies to any platform. SymptomsExpanded mail slot was not scanned, but regular 4 mail slot were scanned. Manual library audit was required to scan tapes in expanded mail slots. No Fault Code available from log bundle.
ChangesNo changes made by customer. CauseFaulty right side magazine sensor on Base module. SolutionReplace Base module. Refer to: SL150 - How To Remove/Replace a Base Module Chassis CRU In the StorageTek SL150 Modular Tape Library [VCAP] (Doc ID 1472418.1)