Solution Type Problem Resolution Sure Solution 2032940.1 : SL8500 - CIM Floor Missing One Alignment Slot for Inner Wall
In this Document
Oracle Confidential PARTNER - Available to partners (SUN). Applies to:Sun StorageTek SL8500 Modular Library System - Version All Versions and laterInformation in this document applies to any platform. SymptomsCIM Floor Missing One Alignment Slot for Inner Wall. The right side of the wall cannot be latched as a result. The slot/tabs serve no structural purpose and are used for setting the correct orientation of the wall during assembly. The remaining two slots are sufficient for this purpose. The Southco latches are what align and hold the center wall in place. See image below to identify the missing slot: ChangesNew Install of library. Cause Several CIM floors were manufactured that are missing the slot engaged by the right tab at the bottom of the CIM inner wall. SolutionResolution -The following procedure has been used successfully in the field as a workaround for this issue. Also attached is a PDF file with a similar alternate solution that bends the tab instead of removing it.