Solution Type Problem Resolution Sure Solution 2009033.1 : Infiniband Switch showunhealthy Message "Flash disk has bad blocks"
In this Document
Created from <SR 3-10635198763> Applies to:Exadata Database Machine X2-2 Hardware - Version All Versions and laterSun Datacenter InfiniBand Switch 36 - Version All Versions and later Sun Network QDR InfiniBand Gateway Switch - Version All Versions and later Information in this document applies to any platform. Symptomsshow unhealthy command gives the following: #showunhealthy
env_test output also shows problems with internal disk: #env_test
And, ILOM snapshot shows: < @usr@local@bin@spshexec_show_faulty.out>
ChangesThe message is showing for the first time. CauseThe internal hard disk of this switch has failed, or has bad blocks and needs to be replaced before full failure. SolutionInternal hard disk is not a field replaceble unit. The infiniband switch will have to be replaced. So, the solution is to replace the infiniband switch References<NOTE:1383773.1> - How to Replace a Failed Sun Network QDR InfiniBand Gateway SwitchAttachments This solution has no attachment |
||||||||||||||||||||
|