Solution Type  Problem Resolution Sure

Solution  2009033.1 :   Infiniband Switch showunhealthy Message "Flash disk has bad blocks"  


Related Items
  • Sun Datacenter InfiniBand Switch 36
  •  
  • Exadata Database Machine X2-2 Hardware
  •  
  • Sun Network QDR InfiniBand Gateway Switch
  •  
Related Categories
  • PLA-Support>Sun Systems>SAND>Network>SN-SND: Sun Network Infiniband
  •  




In this Document
Symptoms
Changes
Cause
Solution
References


Created from <SR 3-10635198763>

Applies to:

Exadata Database Machine X2-2 Hardware - Version All Versions and later
Sun Datacenter InfiniBand Switch 36 - Version All Versions and later
Sun Network QDR InfiniBand Gateway Switch - Version All Versions and later
Information in this document applies to any platform.

Symptoms

 show unhealthy command gives the following:

#showunhealthy
WARNING Flash disk has bad blocks   <<<<<<
FAILURE - 1 sensors NOT OK

 

env_test output also shows problems with internal disk:

#env_test
(Snipe..)
Starting SSD test:
WARNING Flash disk has bad blocks   <<<<<
SSD test returned 1 faults
Environment test FAILED

 

And, ILOM snapshot shows:

< @usr@local@bin@spshexec_show_faulty.out>
-> show faulty
Target | Property | Value
--------------------+------------------------+---------------------------------
/SP/faultmgmt/0 | fru | /SYS/MB
/SP/faultmgmt/0/ | class | fault.chassis.io.disk.predictive    <<<<<<<
faults/0 | | -failure                                                     <<<<<<<
/SP/faultmgmt/0/ | sunw-msg-id | DCSIB-8000-3Y
faults/0 | |
/SP/faultmgmt/0/ | uuid | f8a5b814-994d-44b2-8d0c-b3886489
faults/0 | | 0437
/SP/faultmgmt/0/ | timestamp | 2015-04-21/13:26:27
faults/0 | |
/SP/faultmgmt/0/ | fru_part_number | 5111232
faults/0 | |
/SP/faultmgmt/0/ | fru_serial_number | 0110SJC-10103P0416
faults/0 | |
/SP/faultmgmt/0/ | product_serial_number | 0110SJC-10103P0416
faults/0 | |
/SP/faultmgmt/0/ | chassis_serial_number | 0110SJC-10103P0416
faults/0 | |

 

Changes

The message is showing for the first time.

Cause

 The internal hard disk of this switch has failed, or has bad blocks and needs to be replaced before full failure.

Solution

Internal hard disk is not a field replaceble unit.  The infiniband switch will have to be replaced.

So, the solution is to replace the infiniband switch

References

<NOTE:1383773.1> - How to Replace a Failed Sun Network QDR InfiniBand Gateway Switch