Solution Type Problem Resolution Sure Solution 1991043.1 : T10000A and T10000B - Stiction Issues
In this Document
Applies to:Sun StorageTek T10000A Tape Drive - Version All Versions to All Versions [Release All Releases]Sun StorageTek T10000B Tape Drive - Version All Versions to All Versions [Release All Releases] Information in this document applies to any platform. SymptomsStiction related perm errors on T10000A and T10000B tape drives. FSC: 5809 SRV_FSC_UNWIND_RECOVERY_STALLED_EARLY CauseTape stiction problem. This is caused by the tape getting stuck to the drive heads. SolutionFor any of the above stiction related FSCs (as a permanent error) do the following: 1. Ensure that the drives are running at 1.48.x05 code. (or higher) 2. Determine which tapes are involved. Check the history of the failing tapes to see if they are failing on other drives as well. If the tape is failing on other drives then this is a media problem. This can be accomplished using host logs or by using STA. 3. If the drive experiences 4 or more perm errors on unique tapes then this SR needs to be sent to an L2 Domain rep for drive replacement verification. Attachments This solution has no attachment |
||||||||||||||||
|