Oracle Confidential PARTNER - Available to partners (SUN). Applies to:Sun StorageTek SL8500 Modular Library System - Version All Versions and laterInformation in this document applies to any platform. SymptomsSL8500 Power Strips May Be Too Thick To Install. A set of 3EF-313924302 power strips were received with a new installation and the plastic casing was found to be too thick to install on several strips. Replacement strips were required. ChangesInstall of library. CauseManufacturing issue with the power strips. SolutionUntil further notice make sure you inspect the power strips as soon as possible after the delivery of a new SL8500 or expansion upgrade. You will need to unpack the strips and either check that every strip will freely slide into the rails or they can be measured if a caliper is available. The maximum thickness of a power strip is .230" (5.84 mm). If the strips are too thick order replacements. There were both good and bad strips with the same date code so that is not a valid means of determining if the strips are usable. Attachments This solution has no attachment |
||||||||||||||||||
|