Solution Type  Problem Resolution Sure

Solution  1664265.1 :   System Won't Start Due To Temperature Thresholds  


Related Items
  • Sun Netra 440 Server
  •  
Related Categories
  • PLA-Support>Sun Systems>SPARC>Workgroup Servers>SN-SPARC: SF-V4x0
  •  




In this Document
Symptoms
Cause
Solution


Created from <SR 3-8612172731>

Applies to:

Sun Netra 440 Server - Version All Versions to All Versions [Release All Releases]
Information in this document applies to any platform.

Symptoms

Server not powering on due to high soft shutdown thresholds

SC Alert: TEMP_SENSOR @ C1.P0.T_CORE has exceeded high soft shutdown threshold.
Hardware watchdog enabled
SC unretrieved msg FEB 26 02:49:45 2014 UTC [CRITICAL ALARM is set]
SC unretrieved msg FEB 26 04:23:34 2014 UTC [TEMP_SENSOR @ C1.P0.T_CORE has exceeded high warning threshold.]
SC unretrieved msg FEB 26 04:23:46 2014 UTC [TEMP_SENSOR @ C0.P0.T_CORE has exceeded high warning threshold.]
SC unretrieved msg FEB 26 04:23:59 2014 UTC [SC initiating soft host system shutdown due to fault at C1.P0.T_CORE.]
SC unretrieved msg FEB 26 04:24:01 2014 UTC [TEMP_SENSOR @ C1.P0.T_CORE has exceeded high soft shutdown threshold.]
TEMP_SENSOR @ C0.P0.T_CORE has exceeded high soft shutdown threshold.

 

Cause

Server is down due to the fan tray (FT0) failure.
 

sc> showlogs

Log entries since FEB 26 04:19:17
----------------------------------
FEB 26 04:19:17 Hostname: 0004004f: "Indicator SYS.SERVICE is now ON"
FEB 26 04:19:17 Hostname: 0004004f: "Indicator FT0.F0.ACT is now OFF"
FEB 26 04:19:17 Hostname: 0004004f: "Indicator FT0.F0.FAULT is now ON"
FEB 26 04:19:25 Hostname: 00040002: "Host System has Reset"
FEB 26 04:21:32 Hostname: 00040002: "Host System has Reset"
FEB 26 04:23:34 Hostname: 0004006b: "TEMP_SENSOR @ C1.P0.T_CORE has exceeded high warning threshold."
FEB 26 04:23:46 Hostname: 0004006b: "TEMP_SENSOR @ C0.P0.T_CORE has exceeded high warning threshold."
FEB 26 04:23:58 Hostname: 0004006f: "SC initiating soft host system shutdown due to fault at C1.P0.T_CORE."
FEB 26 04:23:59 Hostname: 00040000: "SC Request to Power Off Host."
FEB 26 04:24:00 Hostname: 0004006c: "TEMP_SENSOR @ C1.P0.T_CORE has exceeded high soft shutdown threshold."
FEB 26 04:24:00 Hostname: 0004004f: "Indicator FT1.F0.ACT is now OFF"
FEB 26 04:24:00 Hostname: 0004004f: "Indicator FT2.F0.ACT is now OFF"
 

 

Solution

The failed Blower Assembly [FT0-2]  should be replaced.
 

The CPU Core temp has "exceeded high warning threshold" message is a side effect of the fan failure, and not an indication of a fault in the CPU in this case.