Solution  1645296.1 :   VSM - SIM Error Reported With FSC7E98 or FSC7E99  


Related Items
  • Sun StorageTek VSM5 System
  •  
Related Categories
  • PLA-Support>Sun Systems>TAPE>Virtual Tape>SN-TP: VSM
  •  




In this Document
Symptoms
Cause
Solution


Created from <SR 3-8833347011>

Applies to:

Sun StorageTek VSM5 System - Version All Versions to All Versions [Release All Releases]
Information in this document applies to any platform.

Symptoms

SIM error reported with either FSC7E98 or FSC7E99

Power LED lit

Cause

FSC7E98_MON_SIDE0_AUX_12V_BAD          

           
                The PDU shows that the power supplied to the logic
                card cage power supply fans has tripped a current
                limiting device within the PDU.  Probable causes
                are: Short circuit, fan failure, PDU failure.  This
                failure is reported from the side 0 PDU.

 FSC7E99_MON_SIDE1_AUX_12V_BAD                


                The PDU shows that the power supplied to the logic
                card cage power supply fans has tripped a current
                limiting device within the PDU.  Probable causes
                are: Short circuit, fan failure, PDU failure.  This
                failure is reported from the side 1 PDU.

 

 

Fenced power supply

Solution

Two methods to confirm error and generate an ATR to facilitate repair:

METHOD 1
Connect to the VSM and log into the machine.
Navigate to FRU status screen
Examine the status of FRUs CU.0.PDU0 and CU.0.PDU1:one should be flagged as fenced.
Make note of the exact FRU location that is fenced and the part number of the FRU.
Create Field Task to have the power supply replaced.
Inform customer that the VSM lost one power supply.
The VSM has a failed power supply however the redundant power supply is functioning and there is no impact to production.

End method 1

METHOD 2
NOTE: IF you do not have access to ZENOBIA use SPLAT to crunch files See KM: 1399676.1
1. Get a full set of base files from the VTSS using standard processes.
2. Place files on zenobia using standard filing conventions.
3. Run the crunch_it all script.
   EX: crunch_it all <enter>
4. Review hic.dmp file
   EX: less hic.dmp <enter>
5. Review hic.dmp file specifically the PSA section.
   You should see a Fencing action against CU.0.PDU0 or PDU1 depending on
   which power supply failed.
   EX: Found PSA Action has taken place
       --------------------------------
       11/09/18 15:06:34 PSA 0x7e98 INIT FENCE 0105 27 - CU.0.PDU0

6. Review crnt_fru.lst file to identify the part number of the defective
   power supply.
7. Create Field Task to have the power supply replaced.
8. Inform customer that the VSM lost one power supply.
   The VSM has a failed power supply however the redundant power supply
   is functioning and there is no impact to production.

End method 2

 