Solution Type Problem Resolution Sure Solution 1615216.1 : WARNING Fan x running slow for all 3 fans on InfiniBand Switch
Created from <SR 3-8202917651> Applies to:Exadata Database Machine X2-2 Hardware - Version All Versions to All Versions [Release All Releases]Information in this document applies to any platform. Symptomsenv_test showed:- Starting FAN test: Changesnone CauseThis issue was caused by one of the fans. SolutionEach fan was withdrawn in turn until the remaining 2 fans worked properly. If a know good fan from another switch was used to replace the suspect fan, all 3 fans worked well. As a double check, the suspect fan was placed into another switch and all 3 fans started to run slowly in that switch. References<NOTE:1383752.1> - How To Back Up and Restore Switch Settings for Sun Network QDR InfiniBand Gateway SwitchAttachments This solution has no attachment |
||||||||||||
|