Solution Type Problem Resolution Sure Solution 1606569.1 : All 3 IB Switches on the single rack fabric are LID 0 And SM Master Is Not Running
In this Document
Created from <SR 3-8187344906> Applies to:Exadata X3-2 Hardware - Version All Versions to All Versions [Release All Releases]Information in this document applies to any platform. SymptomsAll 3 IB switches on the fabric are reporting " No Master SubnetManager seen in the system" when running getmaster SMinfo was reporting the following on the spine switch: # sminfo #ibnetdiscover shows "LID 0" for all nodes on the fabric
CauseAdministrator accidentally removed the following line from /etc/hosts: 127.0.0.1 localhost.localdomain localhost SolutionEdit the /etc/hosts file and add the following to the top of the file if it does not exist already: 127.0.0.1 localhost.localdomain localhost Attachments This solution has no attachment |
||||||||||||||||
|