CPU blade failure on Qlogic SANbox 9000 switches after a data center power failure.
Related Items |
- Sun SAN Switch Hardware
- Qlogic SANbox 9100 Switch
|
Related Categories |
- PLA-Support>Sun Systems>DISK>Switch>SN-DK: Qlogic switch
|
In this Document
Created from <SR 3-7975019891>
Applies to:
Sun SAN Switch Hardware - Version All Versions and later
Qlogic SANbox 9100 Switch - Version Not Applicable and later
Information in this document applies to any platform.
Symptoms
After the data center lost power several of the Qlogic switches had CPU cards and I/O cards that showed an Oper State of "Pwrdoff" and a Fault Status of "Fault".
CMD: show blade
----
Blade Blade Port Admin Oper Fault Temp Voltage
ID Type Range State State Status Status Status
----- ----- ----- ----- ----- ------ ------ ------
IO0 FC4G16 0-15 Online Online None Normal Good
IO1 FC4G16 16-31 Online Online None Normal Good
IO2 FC4G16 32-47 Online Online None Normal Good
IO3 FC4G16 48-63 Online Online None Normal Good
IO4 FC4G16 64-79 Online Online None Normal Good
IO5 FC4G16 80-95 Online Online None Normal Good
IO6 FC4G16 96-111 Online Online None Normal Good
IO7 FC4G16 112-127 Online Online None Normal Good
CPU0 * N/A Online PwrdOff Fault * * <--------------Pwrdoff/Fault
+CPU1 CPU N/A Online Online None Normal Good
PS0 PSBF N/A N/A N/A None N/A N/A
PS1 PSBF N/A N/A N/A None N/A N/A
FAN0 FANBF N/A N/A N/A None N/A N/A
FAN1 FANBF N/A N/A N/A None N/A N/A
MP MP N/A N/A N/A None N/A N/A
Changes
Power loss in the data center.
Cause
Blade failure caused by datacenter power failure.
Power failure in Data Center - 5 blades in 2 switches and 1 CPU card in another switch did not come up after power restored.
Solution
The failed blades were replaced.