![]() | Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition | ||
|
|
![]() |
||||||||||||||||||
Solution Type Problem Resolution Sure Solution 1593225.1 : SL500 - Failed Initialization During Hand Roll
In this Document
Created from <SR 3-6742764141> Applies to:Sun StorageTek SL500 Modular Library System - Version All Versions and laterInformation in this document applies to any platform. SymptomsFailed Initialization During Hand Roll, motor not working. Service required LED lit on Op Panel. Error in robotic arm. CauseBroken cable (419659601) Cable damaged because it jammed while robot is being pulled back to be removed from library. SolutionCare must be taken in install/removal of robotic module as the flat ribbon cable can be damaged. Should the above symptoms occur, check for cable damage. If damage is found, the robotic module will need to be replaced as the cable is not a replace-able part. Note: Refer to attached document for information regarding where the cable damage occurs. References<NOTE:1377490.1> - SL500/SL3000/SL8500 - Procedure for Collecting One Button Log Snapshot From LibraryAttachments This solution has no attachment |
||||||||||||||||||
|