Solution Type Problem Resolution Sure Solution 1560748.1 : VSM - Cannot clear or GFR no replace a fenced PDU
In this Document
Created from <SR 3-7354065201> Applies to:Sun StorageTek VSM5 System - Version All Versions and laterSun StorageTek VSM4 System - Version All Versions and later Information in this document applies to any platform. SymptomsCannot do Guided Fru Replacement (GFR) on a Power Distribution Unit (PDU) after loosing AC input. Cause
Lost AC input from the customer environment The VSM Power Distribution Unit (PDU) is faulty GFR no replace is not clearing the fenced PDU due to ISP (VSM Support Processor card) requiring to be switched SolutionSteps to clear a fenced PDU after AC power is lost. 1. Check with the customer and insure that the AC power is back. 2. The following steps needs to be done by a Oracle field engineer, open a service request. 3. Do a GFR, No Replace of the failing PDU. 4. If the GFR fails, the ISP may need to be switched to standby and then back to primary ISP. 5. If the ISP switch does not help, the PDU may be faulty. Make a new task on the existing SR, and order a replacement PDU. References<NOTE:1306541.1> - How to Remove and Replace a VSM Fenced FRU:ATR:897:4Attachments This solution has no attachment |
||||||||||||||||||
|