Solution Type Problem Resolution Sure Solution 1550256.1 : T10000 - RTD on Maintenance Mode Caused by the Drive Not Getting Cleaned When Needed
When a Tape Drive is connected to a VSM, and it is having hardware problems like mount/dismount issues, the VTCS will put the RTD in maintenance mode. After the hardware issue has been resolved, the RTD can be put back online in VSM. In this Document
Created from <SR 3-7122580831> Applies to:Sun StorageTek T10000A Tape Drive - Version Not Applicable to Not Applicable [Release N/A]Sun StorageTek T10000B Tape Drive - Version Not Applicable and later StorageTek T10000C Tape Drive - Version Not Applicable and later Sun StorageTek T10000 Tape Drive - Version Not Applicable and later Information in this document applies to any platform. SymptomsRTD (Real Tape Drive) in maintenance mode. FSC3336, 3336 FSC3955, 3955 FSC3992, 3992 Expired cleaning cartridge CauseThe drive needs cleaning: Device Id : 1,1,2,1,1
General Drive Type : T10000a Code Version : 1.48.105-5.30 Vendor : StorageTek Serial Number : 531004001139 Interface Type : Ficon Device Id : 1,1,2,1,1 State Status : ok Op State : online Drive State : empty Drive needs cleaning : true Host Activity : false
...but the cleaning cartridge is expired: The library EventLog - Error Warn Info is showing drive hardware issues like the following: 2013-04-25 17:11:26 Drive_Bay61(1.1.2.1.1)
SolutionEject the expired cleaning cartridge and mount a new one in the drive. References<NOTE:1278426.1> - T10000/9840 - Process For RTD Drives That Are Put Into Maintenance ModeAttachments This solution has no attachment |
||||||||||||||||||
|