Solution Type Problem Resolution Sure Solution 1535176.1 : Pillar Axiom: Temperature warnings, thresholds and required actions
In this Document
Created from <SR 3-6881330801> Applies to:Pillar Axiom 600 Storage System - Version Not Applicable to Not Applicable [Release N/A]Pillar Axiom 500 Storage System - Version All Versions to Not Applicable [Release All Releases to N/A] Information in this document applies to any platform. SymptomsAfter an Air conditioning issue, the Slammer, Pilot of Bricks can be in a Critical or Offline state Cause Temperature has unexpectedly increased in the server room due to the air conditioning issue. SolutionThe Axiom code uses temperature thresholds to decide the actions regarding temperature issues. Reaching one of the thresholds will produce the following action.
The bellow thresholds are internal thresholds temperature sensor and do not reflect the actual temperature in the server room,. Temperature threshold may be subject to change in different firmware but stay in similar ranges. Slammer Thresholds.
1C -- Critical low threshold the Slammer will shut down
Temperature threshold from which the bricks shut down are lower in order to protect the data. SATA disks are spun down and put offline by the firmware before the whole brick is shut down. The system alert of "RAID Array Offline" will be raised when a brick shuts down because of the temperature. At this point all LUNs with data on this brick will be unavailable. ***Please note that on FC bricks, even though the RAID array is offline, the disks are still spinning. SATA version2
FC version 2