Sun Microsystems, Inc.  Oracle System Handbook - ISO 7.0 May 2018 Internal/Partner Edition
   Home | Current Systems | Former STK Products | EOL Systems | Components | General Info | Search | Feedback

Asset ID: 1-72-1475304.1
Update Date:2017-04-25
Keywords:

Solution Type  Problem Resolution Sure

Solution  1475304.1 :   One of the Power Distribution Units (PDU) is non-responsive In Exalogic Rack & Exadata Database Machine  


Related Items
  • Oracle Exadata Hardware
  •  
  • Oracle Exalogic Elastic Cloud Software
  •  
  • Exalogic Elastic Cloud X5-2 Hardware
  •  
  • Exalogic Elastic Cloud X4-2 Hardware
  •  
  • Oracle Exalogic Elastic Cloud X2-2 Hardware
  •  
  • Exalogic Elastic Cloud X3-2 Hardware
  •  
Related Categories
  • PLA-Support>Eng Systems>Exalogic/OVCA>Oracle Exalogic>MW: Exalogic Core
  •  
  • _Old GCS Categories>ST>Server>Engineered Systems>Exadata>Hardware
  •  




In this Document
Symptoms
Cause
Solution
References


Created from <SR 3-5674261771>

Applies to:

Oracle Exadata Hardware - Version 11.1.0.6 and later
Oracle Exalogic Elastic Cloud Software - Version 1.0.0.0.0 and later
Oracle Exalogic Elastic Cloud X2-2 Hardware - Version X2 and later
Exalogic Elastic Cloud X3-2 Hardware - Version X3 to X3 [Release X3]
Exalogic Elastic Cloud X4-2 Hardware - Version X4 to X4 [Release X4]
Oracle Solaris on x86-64 (64-bit)
Linux x86-64

Symptoms

Each Exalogic/Exadata machine (eighth/quarter/half/full) rack has 2 Power Distribution Units (PDU) supplies in each component (InfiniBand Switch/Gateway, Compute Node and Storage head) actively balance power - if one fails, or is connected to a PDU that fails, the other takes over (2N redundancy, continuous availability). Exalogic Power Distribution Units in each Exalogic rack configuration is redundant. For complete redundancy, each PDU should be wired to a different AC source.

One of the Power Distribution Units (PDU) seems to be non-responsive on Exalogic Rack Machine. The firmware version of Exalogic machine PDU is 1.0.4. Following symptoms were observers during the issue.

  • Power Distribution Units LCD panel was dead (i.e. blank)
  • Power Distribution Units HTTP interface become non-responsive for a long period of time.
  • Power Distribution Units interface still responds to PING packets even though the HTTP interface was slow/non-responding.

The issue was not affecting power supply to Exalogic Rack Machines, but merely affecting the ability to monitor current draw through the PDU.

Cause

The Power Distribution Units (PDU) metering unit might have trouble.
 

Solution

Workaround: Please reset the PDU Metering Unit. This can be done without any system down for any servers. In other words, to reset the PDU Metering Unit does not affect to power distribution to the servers.

1. Press and hold the reset button until you see a five-second countdown displayed on the LCD screen, as shown in the following PDU Metering Unit LCD Screen and Reset Button. You must press the reset button for 20 seconds before the five-second countdown begins.  After reset is completed we can press the button for one second repeatedly to reset the display orientation to desired preference:

Note:

It might take 15 - 20 Seconds for the reset procedure to start.

 

2. During the five-second countdown, release the reset button and then tap the button again to force the metering unit to reset.

Please review PDU Documentation (section "Reset the PDU Metering Unit") , which describes the instructions for resetting the PDU Metering Unit: http://docs.oracle.com/cd/E19657-01/html/E23956/z40000521016149.html

References

<BUG:11850025> - RACK PDU CURRENT MONITOR NO LONGER FUNCTIONS

Attachments
This solution has no attachment
  Copyright © 2018 Oracle, Inc.  All rights reserved.
 Feedback