Solution Type Problem Resolution Sure Solution 1386616.1 : Sun Storage 7000 Unified Storage System: Thermal Events and Ongoing Fan issues on 7410/7110 storage arrays
In this Document
Created from <SR 3-5023454061> Applies to:Sun Storage 7110 Unified Storage System - Version Not Applicable to Not Applicable [Release N/A]Sun Storage 7410 Unified Storage System - Version Not Applicable to Not Applicable [Release N/A] 7000 Appliance OS (Fishworks) SymptomsThermal shutdown events reported on Sun Storage 7410 Unified Storage and Sun Storage 7110 Unified Storage System arrays. [logmgr: ID = 7401 : Wed Dec 7 07:02:21 2011 : IPMI : Log : critical : ID = 3a4 : 12/07/2011 : 07:02:21 : Temperature : sys.t_amb : Upper Critical going high : reading 44 > threshold 40 degrees C]
If you see multiple External sensors fan errors at FM 0 + FM 1 + FM 2 at same time then this can be BUG 6925325 iLOM prompt: reset /SP/
CLI> Maintenance - hardware - select - chassis-000 - select - SP - reset ChangesPrevious SR's dealt with Fan issues and a reported Service Processor Memory leak situation that was resolved with an SP reset. To find the SP-IP adress go to Web Gui:
Maintenance --> Hardware-> select the Head-> go to "Show Details" -> go to "SP" Login with sunservice@SP_ip-adress (root password)
(flash)root@v-ss7110b-sp-gmp03:~# 1. /usr/local/bin/collectDebugInfo.sh CauseA number of known issues exist for the 7x10 array, relating to memory leaks on the Service Processor. Over time memory becomes depleted and the Service Processor becomes unresponsive and/or hangs. Note that # reset /SP only restarts the Service Processor and # reset /SYS only restarts the system part of the chassis.
389 | 12/06/2011 | 21:46:52 | Temperature #0x03 | Upper Critical going high
38a | 12/06/2011 | 21:46:59 | Temperature #0x03 | Upper Critical going low 38b | 12/06/2011 | 21:50:44 | Temperature #0x03 | Upper Critical going high 38c | 12/06/2011 | 21:50:49 | Temperature #0x03 | Upper Critical going low 38d | 12/06/2011 | 21:58:06 | Temperature #0x03 | Upper Critical going high 38e | 12/06/2011 | 21:58:11 | Temperature #0x03 | Upper Non-recoverable going high 38f | 12/06/2011 | 21:58:18 | Temperature #0x03 | Upper Non-recoverable going low 390 | 12/06/2011 | 21:58:24 | Temperature #0x03 | Upper Critical going low 391 | 12/06/2011 | 21:58:48 | System ACPI Power State #0xfb | S5/G2: soft-off | Asserted 392 | 12/07/2011 | 06:57:15 | System ACPI Power State #0xfb | S0/G0: working | Asserted 393 | 12/07/2011 | 06:57:15 | System Boot Initiated #0x01 | Initiated by power up | Asserted 394 | 12/07/2011 | 06:57:18 | Processor #0x02 | Presence detected | Asserted 3ae | 12/07/2011 | 07:05:32 | System ACPI Power State #0xfb | S5/G2: soft-off | Asserted 3af | 12/07/2011 | 10:33:16 | Entity Presence #0x46 | Device Present 3b0 | 12/07/2011 | 10:33:16 | System ACPI Power State #0xfb | S5/G2: soft-off | Asserted 3b1 | 12/07/2011 | 10:33:21 | Entity Presence #0x50 | Device Present 3b2 | 12/07/2011 | 11:56:04 | System ACPI Power State #0xfb | S0/G0: working | Asserted 3b3 | 12/07/2011 | 11:56:06 | System Boot Initiated #0x01 | Initiated by power up | Asserted SolutionInitial system boot issues were worked around after performing a #reset /SYS and Sun Storage 7410 Unified Storage System or Sun Storage 7110 Unified Storage System rebooted successfully, but within 10 minutes, the customer reported further temperature over heating issues followed by a shut down again.
If nothing is causing concern there, we have faulty Hardware. This is NOT the known memory leak situation as customers array has SP/BIOS fixes for this..
sp_version: '2.0.2.16', fw_version: '0ABMN080', os_version: 'ak/generic@2010.08.17.2.1,1-1.21',
541-2211, FRU Fan Board, RoHS:Y Culprit
541-2213, FRU Connector Board Assembly, PATA DVDVictim
References<NOTE:1004226.1> - ILOM Service Processor sunservice commands for Sun Fire[TM] X4100 Server (applies to SFX4200/SFX4500/SFX4600 also)<NOTE:1168273.1> - Sun Storage 7000 Unified Storage System: Service Processor (SP) Issues <NOTE:1324444.1> - Sun Storage 7000 Unified Storage System: Fan Troubleshooting <NOTE:1496283.1> - Sun 7000 Unified Storage System: ASR Fan Alarm Verification <BUG:15621864> - SUNBT6925325 ELWOOD (2U) CHASSIS FAN BOARD INTERMITTENTS CAUSING FANS TO "DISSAP Attachments This solution has no attachment |
||||||||||||||||||||
|