How To resolve 3 X Power supply units marked as failed on M8000/M9000 running on single phase
Related Items |
- Sun SPARC Enterprise M9000-32 Server
- Sun SPARC Enterprise M8000 Server
- Sun SPARC Enterprise M9000-64 Server
|
Related Categories |
- PLA-Support>Sun Systems>SPARC>Enterprise>SN-SPARC: Mx000
|
To make aware that if 3 x PSUs are marked as failed on M8000/M9000 that this may not be an issue with the Power Supply Units or the Power Backplane and is most likely an issue with the input feed or a failed ACS.
In this Document
Applies to:
Sun SPARC Enterprise M9000-32 Server - Version Not Applicable to Not Applicable [Release N/A]
Sun SPARC Enterprise M8000 Server - Version Not Applicable to Not Applicable [Release N/A]
Sun SPARC Enterprise M9000-64 Server - Version Not Applicable to Not Applicable [Release N/A]
SPARC
Symptoms
3 x Power Supply Units (PSUs) failed on M8000/M9000 running on Single-Phase power.
Three-Phase power has a single ACS_D ( Three-Phase to Single-Phase convertor) to control each PSU directly.
Changes
ACS failure, Customers input feed has no power or the breaker switch is off.
Cause
When a M8000 or M9000 system with single phase power has 3 x PSUs failed like below.
PSU#40 Status:Normal; Serial:FA0838V475;
+ FRU-Part-Number:CA01022-0690 16H /371-2219-08 ;
+ Power_Status:Input fail;
PSU#41 Status:Normal; Serial:FA0838V510;
+ FRU-Part-Number:CA01022-0690 16H /371-2219-08 ;
+ Power_Status:Input fail;
PSU#42 Status:Normal; Serial:FA0842W950;
+ FRU-Part-Number:CA01022-0690 16H /371-2219-08 ;
+ Power_Status:Input fail;
This can be caused by a input feed to the cabinet failing or a failed AC section (ACS)
To explain this correctly each input feed of the ACS powers 3 power back plane connectors, these can be on different back planes.
If you are seeing the following then the breaker on the ACS has been switched off.
PSU#40 Status:Normal; Serial:FA06373786;
+ FRU-Part-Number:CA01022-0690 10G /371-2219-07 ;
+ Power_Status:Breaker off;
PSU#41 Status:Normal; Serial:FA06374281;
+ FRU-Part-Number:CA01022-0690 10G /371-2219-07 ;
+ Power_Status:Breaker off;
PSU#42 Status:Normal; Serial:FA06374236;
+ FRU-Part-Number:CA01022-0690 10G /371-2219-07 ;
+ Power_Status:Breaker off;
i.e.
M8000 Uses ACS_A (3 input feeds)
-----------------------------------
PSU | ACS input
-----------------------
0,1,2 | 0 (bottom of main power ACS)
3,4,5 | 1 (middle of main power ACS)
6,7,8 | 2 (top of main power ACS)
40,41,42 | 20 (right hand side of dual power ACS) (ACS_C )
43,44,45 | 21 (Middle of dual power ACS)(ACS_C )
46,47,48 | 22 (left hand side of dual power ACS)(ACS_C )
M9000 Uses ACS_B (5 input feeds)
-----------------------------------
PSU | ACS input
-----------------------
0,1,2 | 0 (Left of main power ACS)
3,4,5 | 1 (2nd from Left of main power ACS)
6,7,8 | 2 (Center of main power ACS)
9,10,11 | 3 (2nd from Right of main power ACS)
12,13,14 | 4 (Right of main power ACS)
40,41,42 | 20 (bottom of dual power ACS)
43,44,45 | 21 (2nd from bottom of dual power ACS)
46,47,48 | 22 (center of dual power ACS)
49,50,51 | 23 (2nd from top of dual power ACS)
52,53,54 | 24 (top of dual power ACS)
M9000 Second Cabinet Uses ACS_B (5 input feeds)
---------------------------------------------
PSU | ACS input
-----------------------
20,21,22 | 10 (Left of main power ACS)
23,24,25 | 11 (2nd from Left of main power ACS)
26,27,28 | 12 (Center of main power ACS)
29,30,31 | 13 (2nd from Right of main power ACS)
32,33,34 | 14 (Right of main power ACS)
60,61,62 | 30 (bottom of dual power ACS)
63,64,65 | 31 (2nd from bottom of dual power ACS)
66,67,68 | 32 (center of dual power ACS)
69,70,71 | 33 (2nd from top of dual power ACS)
72,73,74 | 34 (top of dual power ACS)
If a single PSU has the error Input failed then this is likely to be an issue with the PSU itself if this is on Single-Phase or an issue with the ACS_D if this is Three-Phase.
PSU#42 Status:Normal; Serial:FA0842W950;
+ FRU-Part-Number:CA01022-0690 16H /371-2219-08 ;
+ Power_Status:Input fail;
Please check the showhardconf output to determine what Phase of electric is being used
XSCF>showhardconf
SPARC Enterprise M9000;
+ Serial:PA30601004; Operator_Panel_Switch:Locked;
+ Power_Supply_System:Single-1Phase; Ex:Single-1Phase; SCF-ID:XSCF#0;
+ System_Power:On; System_Phase:Cabinet Power On;
Domain#0 Domain_Status:Running;
Solution
Customer needs to check there is power at the input feed and that the switch on the ACS is switched on.
If these are confirmed to be ok then the ACS would need to be replaced.
If your system is having an issue with a M3000/M4000/M5000 power supply please see the following document.
<Document 1506069.1> Sun SPARC[TM] Enterprise M3000, M4000, M5000: Troubleshooting AC input failures
References
<NOTE:1506069.1> - Sun SPARC[TM] Enterprise M3000, M4000, M5000: Troubleshooting AC input failures
http://docs.oracle.com/cd/E19415-01/E27467/E27467.pdf#G9.162733
Attachments
This solution has no attachment