Solution Type Problem Resolution Sure Solution 1020543.1 : Sun Fire[TM] 12K/15K/20K/25K: Esmd reports false voltage alarms on HPCI boards
PreviouslyPublishedAs 260468 Applies to:Sun Fire 12K Server - Version All Versions and laterSun Fire 15K Server - Version All Versions and later Sun Fire E20K Server - Version All Versions and later Sun Fire E25K Server - Version All Versions and later All Platforms SymptomsFollowing messages are seen on the SC, indicating a problem with the HPCI board. > A high voltage has been detected on -12VDC, located on HPCI at IO#. The voltage detected is -11.07v; should be -12.60v to -11.40v. HPCI at IO# is being deconfigured and powered off. Check all hardware for the cause. CauseDue to a change in the environmental specification the acceptable range of voltages for the HPCI was adjusted. SolutionBug ID 6841225 is resolved with <Patch 122300-12>. There is no need to replace the HPCI board if the indicated voltage falls within the new range of values. Attachments This solution has no attachment |
||||||||||||
|